29 / 58
Identificazione: MD-AL-GI-00
Rev. 4.0 del 31.01.18 - Applicazione: GID
Manual of 11/06/2019 Rev. 1.8 “User Manual for 3000SP storage inverter”
The table below shows the recommended parameters for PYLONTECH US2000B and US2000 PLUS
batteries:
Number of batteries in parallel
1
2
3
4
Battery type
PYLON
PYLON
PYLON
PYLON
Capacity
50Ah
100Ah
150Ah
200Ah
Maximum charging voltage
53.2V
53.2V
53.2V
53.2V
Maximum charging current
25.0A
50.0A
60.0A
60.0A
Maximum protection voltage
54.0V
54.0V
54.0V
54.0V
Maximum discharge voltage
47.2V
47.2V
47.2V
47.2V
Maximum discharge current
25.0A
50.0A
60.0A
60.0A
Minimum protection voltage
46.0V
46.0V
46.0V
46.0V
Depth of Discharge
80%
80%
80%
80%
For Tawaki Maui 4kWh and Weco ReSU 4k4 batteries, please refer to the relevant datasheets available
4)
Battery capacity (only for DEFAULT batteries)
Use the “Up” and “Down” keys to select the capacity of the battery pack connected to the system, press
“OK” to move to the next value and confirm. Once the setting has been completed, the system will
automatically move to the next section.
5)
Maximum charging voltage [V] (only for DEFAULT batteries)
Use the “Up” and “Down” keys to set the maximum charging voltage for the battery pack connected
to the system (check the battery datasheet), press “OK” to move to the next value and confirm.
Once the setting has been completed, the system will automatically move to the next section.
6)
Maximum charging current [A] (only for DEFAULT batteries)
Use the “Up” and “Down” keys to set the maximum charging current for the battery pack connected
to the system (check the battery datasheet), press “OK” to move to the next value and confirm.
Once the setting has been completed, the system will automatically move to the next section.
7)
Overvoltage threshold [V] (only for DEFAULT batteries)
Use the “Up” and “Down” keys to set the maximum protection voltage for the battery pack
connected to the system (check the battery datasheet), press “OK” to move to the next value and
confirm. Once the setting has been completed, the system will automatically move to the next
section.
8)
Minimum discharging voltage [V] (only for DEFAULT batteries)
Use the “Up” and “Down” keys to set the minimum discharging voltage for the battery pack
connected to the system (check the battery datasheet), press “OK” to move to the next value and
confirm. Once the setting has been completed, the system will automatically move to the next
section.