42 / 58
Identificazione: MD-AL-GI-00
Rev. 4.0 del 31.01.18 - Applicazione: GID
Manual of 11/06/2019 Rev. 1.8 “User Manual for 3000SP storage inverter”
The 3000SP will remain in Standby as long as the energy
produced by the photovoltaic system is less than that requested
by the loads (or the difference is < 100W).
When the energy from the photovoltaic system is greater than
that requested by the loads, the 3000SP will give priority to
charging the battery with the excess energy.
When the battery is fully charged (or when the charging power
is limited), the excess energy will be exported to the grid.
When the energy from the photovoltaic system is once again
lower than that requested by the loads, the system will give
priority to the energy stored in the battery.
When the sum of the energy produced by the photovoltaic
system and supplied by the battery is less than that required by
the loads, the missing energy will be taken from the grid.
Press the “DOWN” key from the main menu to access the
instantaneous information on the operation of the 3000SP.