Object ID
Object Name
Modbus
Address
Active Text
Inactive Text
PV Access
BV92
BYP Remote Xfer Stat
8785H: bit 4
ACTIVE
OFF
R
BV93
BYP Energy Save Stat
8785H: bit 5
ACTIVE
OFF
R
BV94
BYP Motor 1 Sel Stat
8785H: bit 6
SELECT
OFF
R
BV95
BYP Motor 2 Sel Stat
8785H: bit 7
SELECT
OFF
R
BV96
BYP Drive Flt Status
8786H: bit 0
FAULT
OFF
R
BV97
BYP Safety Flt Stat
8786H: bit 1
FAULT
OFF
R
BV98
BYP BAS ILock Status
8786H: bit 2
FAULT
OFF
R
BV99
BYP Ext Fault Stat
8786H: bit 3
FAULT
OFF
R
BV100
Not Used BV100
8786H: bit 4
FAULT
OFF
R
BV101
BYP Motor OL Stat
8786H: bit 5
FAULT
OFF
R
BV102
BYP Motor 1 OL Stat
8786H: bit 6
FAULT
OFF
R
BV103
BYP Mtr 2 OL Stat
8786H: bit 7
FAULT
OFF
R
BV104
BYP Input Phase Loss
8787H: bit 0
FAULT
OFF
R
BV105
BYP Drive Comms
8787H: bit 2
FAULT
OFF
R
BV106
BYP Loss Of Load
8787H: bit 5
FAULT
OFF
R
BV107
BYP Option Brd Comms
8787H: bit 3
FAULT
OFF
R
<1>
Refer to Accessing Bypass Parameters and the Enter Command on page 374
for an explanation of how to read and write drive parameters not
listed in the analog or binary objects.
u
Device Object
The Device Object fully describes the BACnet device to the network. Notable is that the Device Object Instance ID and the
Device Object Name are configurable.
The Device Object Instance ID is a unique internetwork-wide numerical value. It is a 22-bit value that can range from 0 to
4,194,303. It is configurable by parameters Z3-08 and Z3-09. Any changes to these parameters will not take effect until the
power is cycled to the bypass.
The Device Object Name is a unique internetwork-wide character string. It is a 20-character string. It is writable from the
BACnet network. Any new string written will not take effect until the power is cycled to the bypass.
C.6 BACnet Objects Supported
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual