Status
Description
Open
Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed
Output frequency or motor speed is within the range of frequency reference ±L4-02.
Note:
Detection works in forward and reverse.
L4-02
L4-02
Frequency
reference
Speed agree 1
ON
OFF
Output Frequency
Figure 5.24 Speed Agree 1 Time Chart
Setting 3: User-Set Speed Agree 1 (f
ref
/f
set
Agree 1)
The output closes when the actual output frequency or motor speed and the frequency reference are within the speed agree
width (L4-02) of the programmed speed agree level (L4-01).
Status
Description
Open
Output frequency or motor speed and frequency reference are not both within the range of L4-01 ±L4-02.
Closed
Output frequency or motor speed and the frequency reference are both within the range of L4-01 ±L4-02.
Note:
Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
Frequency reference
Frequency reference
+
L4-02
Frequency reference – L4-02
L4-01
L4-01
+
L4-02
L4-01 – L4-02
Frequency reference
Frequency reference
+
L4-02
Frequency reference – L4-02
–L4-01
–L4-01
+
L4-02
–L4-01 – L4-02
During
Forward
During Reverse
Output frequency
0 Hz
OFF
OFF
OFF
ON
ON
ON
ON
Output frequency
User Set
Speed Agree 1
Figure 5.25 User Set Speed Agree 1 Time Chart
Setting 4: Frequency Detection 1
The output opens when the output frequency or motor speed rises above the detection level set in L4-01 plus the detection
width set in L4-02. The terminal remains open until the output frequency or motor speed fall below the level set in L4-01.
Status
Description
Open
Output frequency or motor speed exceeded L4-01 + L4-02.
Closed
Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.
Note:
Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
5.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
155
5
Programming