Setting
Specification
Characteristic
Application
8
50 Hz, Mid starting torque
High starting torque
Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.
9
50 Hz, High starting torque
A
60 Hz, Mid starting torque
B
60 Hz, High starting torque
C
90 Hz (with 60 Hz base)
Constant output
Output voltage is constant when operating at greater than
60 Hz.
D
120 Hz (with 60 Hz base)
E
180 Hz (with 60 Hz base)
F
60 Hz
Variable torque
Used for variable torque applications. The default setting is
the same as V/f pattern Setting 7.
equal to predefined V/f pattern 1.
The following tables show details on predefined V/f patterns.
Predefined V/f Patterns for Models Z1B1D002 to D024 and Z1B1B001 to B011
The values in the following graphs are specific to 208 Vac. Double the values for 480 Vac.
Table 5.8 Constant Torque Characteristics, Settings 0 to 3
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
0
9
200
1.3 2.5
50
15
V
oltage (V)
Frequency (Hz)
0
9
15
200
1.5 3
60
V
oltage (V)
Frequency (Hz)
0
9
15
200
1.5 3
60
50
V
oltage (V)
Frequency (Hz)
0
9
15
200
1.5 3
72
60
V
oltage (V)
Frequency (Hz)
Table 5.9 Variable Torque Characteristics, Settings 4 to 7
Setting = 4
50 Hz
Setting = 5
50 Hz
Setting = 6
60 Hz
Setting = 7
60 Hz
0
8
200
1.3
25
50
35
V
oltage (V)
Frequency (Hz)
0
9
200
1.3
25
50
50
V
oltage (V)
Frequency (Hz)
0
8
200
1.5
30
60
35
V
oltage (V)
Frequency (Hz)
0
9
200
1.5
30
60
50
V
oltage (V)
Frequency (Hz)
Table 5.10 High Starting Torque, Settings 8 to B
Setting = 8
50 Hz
Setting = 9
50 Hz
Setting = A
60 Hz
Setting = B
60 Hz
0
11
200
1.3 2.5
50
19
V
oltage (V)
Frequency (Hz)
0
13
200
1.3 2.5
50
24
V
oltage (V)
Frequency (Hz)
0
11
200
1.5 3
60
19
V
oltage (V)
Frequency (Hz)
0
15
200
1.5 3
60
24
V
oltage (V)
Frequency (Hz)
Table 5.11 Rated Output Operation, Settings C to F
Setting = C
90 Hz
Setting = D
120 Hz
Setting = E
180 Hz
Setting = F
60 Hz
0
9
15
200
1.5 3
90
60
V
oltage (V)
Frequency (Hz)
0
9
15
200
1.5 3
120
60
V
oltage (V)
Frequency (Hz)
0
9
15
200
1.5 3
180
60
V
oltage (V)
Frequency (Hz)
0
10.2
17.3
230
1.5 3
60
V
oltage (V)
Frequency (Hz)
5.6 E: Motor Parameters
146
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Содержание Z1000 CIMR-ZU*A Series
Страница 54: ......
Страница 422: ...E 7 Fault Codes 422 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual...
Страница 463: ...Index This Page Intentionally Blank YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual 463...
Страница 465: ......