6.9 Troubleshooting without Fault Display
This section describes troubleshooting problems that do not trip an alarm or fault.
The following symptoms indicate that the drive is not set correctly for proper performance with the motor.
Performance Fine-Tuning on page 224
for guidance on troubleshooting.
• Motor hunting and oscillation
• Poor motor torque
• Poor speed precision
• Poor motor torque and speed response
• Motor noise
u
Common Problems
Common Problems
Page
Cannot Change Parameter Settings
Motor Does Not Rotate Properly after Pressing the AUTO
Button or after Entering External Run Command
Motor Does Not Rotate
Motor Rotates in the Opposite Direction from the Run
Command
Motor Rotates in One Direction Only
Motor is Too Hot
oPE02 Error Occurs When Lowering the Motor Rated Current Setting
Motor Stalls During Acceleration or With Large Loads
Drive Frequency Reference Differs from the Controller Frequency Reference Command
Excessive Motor Oscillation and Erratic Rotation
Deceleration Takes Longer Than Expected
Noise From Drive or Motor Cables When the Drive is Powered On
Ground Fault Circuit Interrupter (GFCI) Trips During Run
Connected Machinery Vibrates When Motor Rotates
Unexpected Noise from Connected Machinery
Oscillation or Hunting
PI Output Fault
Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection Braking)
Output Frequency is not as High as Frequency Reference
Sound from Motor
Motor Does Not Restart after Power Loss
u
Cannot Change Parameter Settings
Cause
Possible Solutions
The drive is running the motor
(i.e., the Run command is present).
• Stop the drive and switch over to the Programming Mode.
• Most parameters cannot be edited during run.
The operator is not in the Parameter Setup Mode
(the screen will display “PAr”).
• See what mode the operator is currently set for.
• Parameters cannot be edited when in the Setup Mode (“STUP”). Switch modes so that “PAr”
appears on the screen.
Refer to The Drive and Programming Modes on page 99
A multi-function contact input terminal is set to allow
or restrict parameter editing
(H1-01 through H1-07 = 1B).
• When the terminal is open, parameters cannot be edited.
• Turn on the multi-function contact input set to 1B.
The wrong password was entered.
• If the password entered to A1-04 does not match the password saved to A1-05, then drive
settings cannot be changed.
• Reset the password.
If you cannot remember the password:
•
Scroll to Z1-02. Press
OFF
and
simultaneously. Parameter Z1-03 will appear.
• Set a new password to parameter Z1-03.
6.9 Troubleshooting without Fault Display
258
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Содержание Z1000 CIMR-ZU*A Series
Страница 54: ......
Страница 422: ...E 7 Fault Codes 422 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual...
Страница 463: ...Index This Page Intentionally Blank YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual 463...
Страница 465: ......