4.3 The Drive and Programming Modes
The bypass controller has a Drive Mode to operate the motor and a Programming Mode to edit parameter settings..
Drive Mode:
In Drive Mode the user can operate the motor and observe U Monitor parameters. Certain parameter settings
cannot be edited or changed when in Drive Mode.
Programming Mode:
In Programming Mode the user can edit and verify parameter settings and perform Auto-Tuning. When
the drive is in Programming Mode, the “AUTO” and “HAND” keys are ignored.
n
Drive Mode Details
The following actions are possible in the Drive Mode:
• Run and stop the drive
• Monitor the operation status of the drive (frequency reference, output frequency, output current, output voltage, etc.)
• View information on an alarm
• View a history of alarms that have occurred
n
Programming Mode Details
The following actions are possible in the Programming Mode:
•
Parameter Setting Mode:
Access and edit all parameter settings.
•
Modified Constants:
View a list of bypass parameters that have been changed from the default values.
•
Quick Setting Group:
Access a list of commonly used parameters to simplify setup
•
Auto-Tuning Mode:
Automatically calculate and set motor parameters to optimize drive performance.
u
Changing Parameter Settings or Values
This example explains changing C1-02 (Deceleration Time 1) from 30.0 seconds (default) to 20.0 seconds.
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
DRV-OFF
U1-01= 60.00Hz
U1-02= 0.00Hz
U1-03= 0.00 A
Freq Ref (AUTO)
LSEQ
LREF
RLY
DRV/BYP
2.
Press
or
until the Parameter Setting Mode screen appears.
DRV-OFF
Programming
DATA
HELP
3.
Press
to enter the parameter menu tree.
DRV-OFF
Initialize
Bypass Parms
Z
1-01= 0
4.
Press
or
to select the C parameter group.
DRV-OFF
Accel Time 1
Basic Setup
C
1-01= 30.0sec
5.
Press
two times.
DRV-OFF
(0.1-6000.0)
"20.0sec"
Accel Time 1
DRV-OFF
Accel Time 1
Accel/Decel
C
1
-01= 30.0sec
C1-
01
= 30.0sec
6.
Press
or
to select parameter C1-02.
DRV-OFF
(0.1-6000.0)
"30.0sec"
Decel Time 1
C1-
02
= 30.0sec
4.3 The Drive and Programming Modes
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
99
4
Start-Up Programming & Operation
Содержание Z1000 CIMR-ZU*A Series
Страница 54: ......
Страница 422: ...E 7 Fault Codes 422 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual...
Страница 463: ...Index This Page Intentionally Blank YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual 463...
Страница 465: ......