3.6 Bypass and Drive Control I/O Connections
u
Input Signal Selection for Terminals A1 and A2
Terminals A1 and A2 can be used to input either a voltage or a current signal. Select the signal type using jumper S1 as
explained in
. Set parameters H3-01 and H3-09 accordingly as shown in
on the Control Board on page 84
Note:
If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency
reference.
Table 3.12 Jumper S1 Settings
Terminal
Voltage Output
Current Output
Terminal A1
A2
A1
V
I
A2
A1
V
I
Terminal A2
A2
A1
V
I
A2
A1
V
I
Table 3.13 Parameters H3-01 and H3-09 Details
No.
Parameter Name
Description
Setting
Range
Default
Setting
H3-01
Terminal A1 signal level selection
Selects the signal level for terminal A1.
0: 0 to 10 V with Zero Limit
1: 0 to 10 V without Zero Limit
2: 4 to 20 mA Current Input
3: 0 to 20 mA Current Input
0 to 3
0
H3-09
Terminal A2 signal level selection
Selects the signal level for terminal A2.
0: 0 to 10 V with Zero Limit
1: 0 to 10 V without Zero Limit
2: 4 to 20 mA Current Input
3: 0 to 20 mA Current Input
0 to 3
0
u
Terminal FM/AM Signal Selection
The signal type for terminals FM and AM can be set to either voltage or current output using jumper S5 on the terminal board
. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.
The default selection is voltage output for both terminals.
Refer to Switches and Jumpers on the Control Board on page
Table 3.14 Jumper S5 Settings
Terminal
Voltage Output
Current Output
Terminal FM
AM
FM
V
I
AM
FM
V
I
Terminal AM
AM
FM
V
I
AM
FM
V
I
Table 3.15 Parameter H4-07 and H4-08 Details
No.
Parameter Name
Description
Setting
Range
Default
Setting
H4-07
Terminal FM signal level selection
0: 0 to 10 Vdc
2: 4 to 20 mA
0, 2
0
H4-08
Terminal AM signal level selection
3.6 Bypass and Drive Control I/O Connections
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
85
3
Electrical Installation