Point
No.
Point
Type
Point Name
Factory
Default
(SI Units)
Engr. Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
Z1000
Parameter
91
LAO
CBL LOSS
FRQ
0
HZ
0.01
0
–
–
Z3-10
92
LAO
CBL LOSS
TMR
2
SEC
0.1
0
–
–
Z3-06
{93}
LDI
OK.FAULT
OK
–
1
0
FAULT
OK
UB-06 (Bit 2)
{94}
LDO
RESET
FAULT
NO
–
1
0
RESET
NO
–
{95}
LDI
DRV COMM
ERR
NO FLT
–
1
0
FAULT
NO FLT
–
{96}
LDO
EXTERNAL
FLT
OK
–
1
0
FAULT
OK
–
{97}
LDI
MF IN 5
MON
OFF
–
1
0
ON
OFF
UB-02 (Bit 6)
Bypass DI-7
{99}
LAI
ERROR
STATUS
0
–
1
0
–
–
–
<2> Will only report accurately when drive is running.
<3> Point LDI 18 displays both drive alarms and bypass alarms in bypass controller software versions VST800298 and later.
<4> Set Z2-02 to 22 (Run Enable) for point 35 to work properly.
<5> Disabled when Z3-12 is set to 0 in bypass controller software versions VST800298 and later.
E.4 APOGEE FLN Point List Summary
416
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual