B.6 E: Motor Parameters
u
E1: V/f Pattern for Motor 1
No.
(Addr.
Hex)
Name
Description
Values
Page
E1-01
(300)
Input Voltage Setting
Input Voltage
This parameter must be set to the power supply voltage.
WARNING! Electrical Shock Hazard. Drive input voltage (not motor
voltage) must be set in E1-01 for the protective features of the drive to
function properly. Failure to do so may result in equipment damage
and/or death or personal injury.
Min.: 190
Max.: 240
E1-03
(302)
V/f Pattern Selection
V/F Selection
0: 50 Hz, Constant torque 1
0: 50 Hz
1: 60 Hz, Constant torque 2
1: 60 Hz Saturation
2: 50 Hz, Constant torque 3 (50 Hz base)
2: 50 Hz Saturation
3: 72 Hz, Constant torque 4 (60 Hz base)
3: 72 Hz
4: 50 Hz, Variable torque 1
4: 50 Hz VT1
5: 50 Hz, Variable torque 2
5: 50 Hz VT2
6: 60 Hz, Variable torque 3
6: 60 Hz VT1
7: 60 Hz, Variable torque 4
7: 60 Hz VT2
8: 50 Hz, High starting torque 1
8: 50 Hz HST1
9: 50 Hz, High starting torque 2
9: 50 Hz HST2
A: 60 Hz, High starting torque 3
A: 60 Hz HST1
B: 60 Hz, High starting torque 4
B: 60 Hz HST2
C: 90 Hz (60 Hz base)
C: 90 Hz
D: 120 Hz (60 Hz base)
D: 120 Hz
E: 180 Hz (60 Hz base)
E: 180 Hz
F: Custom V/f
F: Custom V/F`
E1-05 setting defines the V/f pattern
Range: 0 to 9;
A to F
E1-05
(304)
Maximum Voltage
Max Voltage
Only applicable when E1-03 is set to F.
Min.: 0.0 V
Max.: 255.0 V
<1> Values shown are specific to 208 Vac. Double the value for 480 Vac.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Default setting is dependent on parameter o2-04, Drive Model Selection.
u
E2: Motor Parameters
No.
(Addr.
Hex)
Name
Description
Values
Page
E2-01
(030E)
Motor Rated Current
Motor Rated FLA
Sets the motor nameplate full load current in amps. Automatically set during
Auto-Tuning.
Default:
Min.: 10% of drive
rated current
Max.: 200% of
drive rated current
E2-03
(310)
Motor No-Load Current
No-Load Current
Sets the no-load current for the motor. Automatically set during Auto-Tuning. Default:
Min.: 0 A
Max.: E2-01
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> The number of decimal places in the parameter value depends on the drive model.
Refer to Defaults by Drive Model on page 356
B.6 E: Motor Parameters
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
321
B
Parameter List