o1-10: User-Set Display Units Maximum Value
Determines the display value that is equal to the maximum output frequency.
No.
Name
Setting Range
Default
o1-10
User-Set Display Units Maximum Value
1 to 60000
Determined by
o1-03
n
o1-11: User-Set Display Units Decimal Display
Determines how many decimal points should be used to set and display the frequency reference.
No.
Name
Setting Range
Default
o1-11
User-Set Display Units Decimal Display
0 to 3
Determined by
o1-03
Setting 0: No Decimal Point
Setting 1: One Decimal Point
Setting 2: Two Decimal Points
Setting 3: Three Decimal Points
u
o2: HOA Keypad Functions
These parameters determine the functions assigned to the operator keys.
n
o2-04: Drive Model Selection
Set this parameter when replacing the control board or the terminal board.
Refer to Defaults by Drive Model on page 356
information on drive model selection.
NOTICE: Drive performance will suffer and protective functions will not operate properly if the correct drive capacity is not set to o2-04.
No.
Name
Setting Range
Default
o2-04
Drive Model Selection
-
Determined by
drive capacity
Note:
Change o2-04 setting only when necessary.
u
o4: Maintenance Monitor Settings
n
o4-03: Cooling Fan Operation Time Setting
Sets the value for how long the cooling fan has been operating. This value can be viewed in monitor U4-03. Parameter o4-03
also sets the base value used for the cooling fan maintenance, which is displayed in U4-04. Reset this parameter to 0 after
replacing the cooling fan.
Note:
1.
The value in o4-03 increases after every 10 hours of use. A setting of 30 will set the cooling fan operation time counter to 300 h. “300”
will be displayed in monitor U4-03.
2.
The cooling fan may require maintenance at an earlier date in harsher environments.
No.
Name
Setting Range
Default
o4-03
Cooling Fan Operation Time Setting
0 to 9999 h
0 h
n
o4-11: U2-
oo
, U3-
oo
, and UB-09 to UB-16 Initialization
Resets the drive and bypass fault trace and fault history monitors.
Note:
1.
Parameter is available in bypass controller software versions VST800298 and later.
2.
Initializing the drive using A1-03 does not reset these monitors.
No.
Name
Setting Range
Default
o4-11
U2, U3, and UB-09 to UB-16 Initialization
0, 1
0
Setting 0: No Action
The drive and bypass keep the previously saved record concerning fault trace and fault history.
5.11 o: Operator-Related Settings
184
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Содержание Z1000 CIMR-ZU*A Series
Страница 54: ......
Страница 422: ...E 7 Fault Codes 422 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual...
Страница 463: ...Index This Page Intentionally Blank YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual 463...
Страница 465: ......