u
Writing to Multiple Registers
Function code 10H allows the user to write multiple MEMOBUS/Modbus registers with one message. This process works
similar to reading registers, in that the address of the first register to be written and the data quantity are set in the command
message. The data to be written must be consecutive so that the register addresses are in order, starting from the specified
address in the command message. The data order must be high byte then lower byte.
The following table shows an example of a message where a forward operation has been set with a frequency reference of
60.0 Hz for the slave 1 drive.
If parameter values are changed using the Write command, an Enter command is necessary to save the data.
Command Message
Response Message (normal)
Response Message (fault)
Slave Address
01H
Slave Address
01H
Slave Address
01H
Function Code
10H
Function Code
10H
Function Code
90H
Starting No.
Upper
00H
Starting No.
Upper
00H
Error Code
02H
Lower
01H
Lower
01H
CRC-16
Upper
CDH
Data Quantity
Upper
00H
Data Quantity
Upper
00H
Lower
C1H
Lower
02H
Lower
02H
Number of Bytes
04H
CRC-16
Upper
10H
Starting Data
Upper
00H
Lower
08H
Lower
01H
Next Data
Upper
02H
Lower
58H
CRC-16
Upper
63H
Lower
39H
Note:
Double the number of the data quantity for the number of bytes in the command message.
D.8 Message Examples
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
391