A.1 Power Ratings
u
Three-Phase 208 Vac Models Z1B1D002 to D046
Table A.1 Power Ratings (Three-Phase 208 V)
Item
Specification
Bypass Model Z1B1
D002
D003
D004
D007
D010
D016
D024
D030
D046
Maximum
Applicable
Motor
Capacity
HP
0.5
0.75
1
2
3
5
7.5
10
15
kW
0.37
0.55
0.74
1.5
2.2
3.7
5.5
7.5
11
Input
Input Current (A)
2.9
4.0
5.1
8.0
11.1
17.2
24.7
31.3
46.7
Rated Voltage
Rated Frequency
Three-phase 208 Vac 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Output
Rated Output Current (A)
2.4
3.5
4.6
7.5
Overload Tolerance
110% of rated output current for 60 s
150% peak
Carrier Frequency
User adjustable between 1 and 12.5 kHz
(Maximum Frequency varies with Rated Output Capacity)
Maximum Output Voltage (V)
Three-phase 208 Vac
Maximum Output Frequency (Hz)
240 Hz
Harmonics
Reduction
DC Link Choke
Built-in
EMC
Filter (IEC/EN 61800-3 Category 2)
Built-in
connections, and power supply impedance.
<3> Carrier frequency is set to 5 kHz. Current derating is required to raise the carrier frequency.
A.1 Power Ratings
300
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Содержание Z1000 CIMR-ZU*A Series
Страница 54: ......
Страница 422: ...E 7 Fault Codes 422 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual...
Страница 463: ...Index This Page Intentionally Blank YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual 463...
Страница 465: ......