Table 5.21 Multi-Function Digital Output Terminal Settings
Setting
Function
Page
0
During Run 1
1
Zero Speed
2
Speed Agree 1
3
User-Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock 1 (N.O.)
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
E
Fault
F
Through Mode
10
Minor Fault
11
Fault Reset Command Active
13
Speed Agree 2
Setting
Function
Page
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
1A
During Reverse
1B
During Baseblock 2 (N.C.)
1E
Restart Enabled
20
Drive Overheat Pre-Alarm (oH)
2F
Maintenance Period
37
During Run 2
39
Watt Hour Pulse Output
3D
During Speed Search
4C
During Fast Stop
4D
oH Pre-Alarm Time Limit
60
Internal Cooling Fan Alarm
100 to 160 Functions 0 to 60 with Inverse Output
Setting 0: During Run
The output closes when the drive is outputting a voltage.
Status
Description
Open
Drive is stopped.
Closed
A Run command is input or the drive is in deceleration or DC injection.
ON
ON
OFF
OFF
ON
OFF
Run command
Baseblock
command
Output
frequency
During Run
Figure 5.22 During Run Time Chart
Setting 1: Zero Speed
The output closes when the output frequency or motor speed falls below the minimum output frequency set to E1-09 or b2-01.
Status
Description
Open
Output frequency is above the minimum output frequency set to E1-09 or b2-01
Closed
Output frequency is less than the minimum output frequency set to E1-09 or b2-01
OFF
Output frequency
Zero Speed
ON
E1-09 (Min. Output Frequency) or
b2-01 (Zero Speed Level)
Figure 5.23 Zero-Speed Time Chart
Setting 2: Speed Agree 1 (f
ref
/f
out
Agree 1)
The output closes when the actual output frequency or motor speed is within the Speed Agree Width (L4-02) of the current
frequency reference regardless of the direction.
5.8 H: Terminal Functions
154
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Содержание Z1000 CIMR-ZU*A Series
Страница 54: ......
Страница 422: ...E 7 Fault Codes 422 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual...
Страница 463: ...Index This Page Intentionally Blank YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual 463...
Страница 465: ......