u
Three-Phase 480 Vac Models Z1B1B001 to B034
Table A.3 Power Ratings (Three-Phase 480 V)
Item
Specification
Bypass Model Z1B1
B001
B002
B003
B004
B007
B011
B014
B021
B027
B034
Maximum
Applicable
Motor
Capacity
HP
0.75
1
2
3
5
7.5
10
15
20
25
kW
0.55
0.74
1.5
2.2
3.7
5.5
7.5
11
14.7
18.4
Input
Input Current (A)
1.8
2.3
3.6
5.0
7.8
11.2
14.2
21.2
27.2
34.2
Rated Voltage
Rated Frequency
Three-phase 480 Vac 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Output
Rated Output Current (A)
2.1
4.8
14.0
27.0
Overload Tolerance
110% of rated output current for 60 s
150% peak
Carrier Frequency
User adjustable between 1 and 12.5 kHz
(Maximum Frequency varies with Rated Output Capacity)
Maximum Output Voltage (V)
Three-phase 480 V
Maximum Output Frequency (Hz)
240 Hz
Harmonics
Reduction
DC Link Choke
Built-in
EMC
Filter (IEC/EN 61800-3 Category 2)
Built-in
connections, and power supply impedance.
<3> Carrier frequency is set to 5 kHz. Current derating is required to raise the carrier frequency.
A.1 Power Ratings
302
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Содержание Z1000 CIMR-ZU*A Series
Страница 54: ......
Страница 422: ...E 7 Fault Codes 422 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual...
Страница 463: ...Index This Page Intentionally Blank YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive Z1000 Bypass Technical Manual 463...
Страница 465: ......