5.10 o: Operator Related Settings
YASKAWA ELECTRIC
SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
247
P
a
ra
me
te
r D
e
ta
ils
5
n
o2-06: Operation Selection when Digital Operator is Disconnected
Determines if the drive will stop when the digital operator is removed in LOCAL mode or when b1-02 or b1-16 is set to
0. When the operator is reconnected, the display will indicate that it was disconnected.
Setting 0: Continue operation
The operation is continued.
Setting 1: Trigger a fault
The operation is stopped and an “oPr” fault is triggered. The motor coasts to stop.
n
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up and the Run command is given from the
digital operator.
Note:
This parameter is effective only when the Run command is set to be given from the digital operator (b1-02, b1-16 = 0).
Setting 0: Forward
Setting 1: Reverse
u
o3: Copy Function
These parameters control the digital operator’s Copy function. The Copy function lets the user store all parameter
settings into the memory of the digital operator, and easily transfer those settings to other drives (requires that the other
drives be the same model, capacity, and have the same control mode setting). See
Copy Function Related Displays on
for a description of errors and displays.
n
o3-01 Copy Function Selection
Setting o3-01 will instruct the drive to Read, Write, or Verify parameters settings.
Setting 0: Copy Select (no function)
Setting 1: INV
→
OP READ
All parameters are copied from the drive to the digital operator.
Note:
The copy protection for the digital operator is enabled by default. To unlock copy protection, set o3-01 = 1.
Setting 2: OP
→
INV WRITE
All parameters are copied from the digital operator to the drive.
Setting 3: OP
↔
INV VERIFY
Parameters in the drive are compared with the parameter settings saved on the digital operator to see if they match.
n
o3-02 Copy Allowed Selection
Restricts or allows the use of the Copy function.
Setting 0: Disabled
Setting 1: Enabled
No.
Name
Setting Range
Default
o2-06
Digital Operator Disconnection Operation
0 or 1
0
No.
Name
Setting Range
Default
o2-07
Motor Direction at Power Up when Using Operator
0 or 1
0
No.
Name
Setting Range
Default
o3-01
Copy Function Selection
0 to 3
0
No.
Name
Setting Range
Default
o3-02
Copy Allowed Selection
0 or 1
0
Содержание T1000A
Страница 4: ...4 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 32: ...1 5 Component Names 32 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 104: ...4 10 Test Run Checklist 104 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 334: ...7 5 Drive Replacement 334 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 362: ...A 6 Drive Derating Data 362 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...