B.5 Parameter Defaults Determined by Drive Model (o2-04) and Duty Rating (C6-01)
428
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
Table B.6 400 V Class Drives Default Settings by Drive Capacity and ND/HD Setting
No.
Name
Unit
Default Settings
–
Model CIMR-T
–
4A0002
4A0004
4A0005
4A0007
C6-01
Drive Duty Selection
–
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
o2-04
Drive Model Selection
Hex.
92
93
94
95
E2-11 (E4-11)
Motor rated power
kW
0.4
0.75
0.75
1.5
1.5
2.2
2.2
3.0
b3-04
V/f Gain during Speed Search
%
100
100
100
100
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
Energy Saving Control Filter Time Constant
s
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
Energy Saving Coefficient Value
–
576.4
447.4
447.4
338.8
338.8
313.6
313.6
265.7
C5-17 (C5-37)
Motor Inertia
kgm
2
0.0015
0.0028
0.0028
0.0068
0.0068
0.0088
0.0088
0.0158
C6-02
Carrier Frequency Selection
–
1
1
1
1
1
1
1
1
E2-01 (E4-01)
Motor Rated Current
A
1
1.6
1.6
3.1
3.1
4.2
4.2
5.7
E2-02 (E4-02)
Motor Rated Slip
Hz
2.9
2.6
2.6
2.5
2.5
3
3
2.7
E2-03 (E4-03)
Motor No-Load Current
A
0.6
0.8
0.8
1.4
1.4
1.5
1.5
1.9
E2-05 (E4-05)
Motor Line-to-Line Resistance
Ω
38.198
22.459
22.459
10.1
10.1
6.495
6.495
4.360
E2-06 (E4-06)
Motor Leakage Inductance
%
18.2
14.3
14.3
18.3
18.3
18.7
18.7
19
E2-10 (E4-10)
Motor Iron Loss for Torque Compensation
W
14
26
26
53
53
77
77
105
E5-01
Motor Code Selection
Hex.
1232
1232
1233
1233
1235
1235
1236
1236
L2-02
Momentary Power Loss Ride-Thru Time
s
0.1
0.1
0.2
0.2
0.3
0.3
0.5
0.5
L2-03
Momentary Power Loss Min. Baseblock Time
s
0.2
0.3
0.3
0.4
0.4
0.5
0.5
0.5
L2-04
Momentary Power Loss Voltage Recovery Time
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L8-02
Overheat Alarm Level
°
C
110
110
110
110
110
110
110
110
L8-35
Installation Method Selection
–
2
2
2
2
2
2
2
2
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
2
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
10
10
10
n5-02
Motor Acceleration Time
s
0.178
0.142
0.142
0.166
0.166
0.145
0.145
0.145
n9-12
On-Delay Compensation Time
μ
s
1.5
1.5
1.5
1.5
1.7
1.7
1.7
1.7
S6-01
DC Bus Capacity
μ
F
250
250
250
250
250
250
375
375
S6-02
Motor Acceleration Time
s
0.178
0.142
0.142
0.166
0.166
0.145
0.145
0.145
No.
Name
Unit
Default Settings
–
Model CIMR-T
–
4A0009
4A0011
4A0018
4A0023
C6-01
Drive Duty Selection
–
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
o2-04
Drive Model Selection
Hex.
96
97
99
9A
E2-11 (E4-11)
Motor Rated Power
kW
3.0
3.7
3.7
5.5
5.5
7.5
7.5
11
b3-04
V/f Gain during Speed Search
%
100
100
100
100
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
Energy Saving Control Filter Time Constant
s
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
Energy Saving Coefficient Value
–
265.7
245.8
245.8
189.5
189.5
145.38
145.38
140.88
C5-17 (C5-37)
Motor Inertia
kgm
2
0.0158
0.0158
0.0158
0.0255
0.026
0.037
0.037
0.053
C6-02
Carrier Frequency Selection
–
1
1
1
1
1
1
1
1
E2-01 (E4-01)
Motor Rated Current
A
5.7
7
7
9.8
9.8
13.3
13.3
19.9
E2-02 (E4-02)
Motor Rated Slip
Hz
2.7
2.7
2.7
1.5
1.5
1.3
1.3
1.7
E2-03 (E4-03)
Motor No-Load Current
A
1.9
2.3
2.3
2.6
2.6
4
4
5.6
E2-05 (E4-05)
Motor Line-to-Line Resistance
Ω
4.360
3.333
3.333
1.595
1.595
1.152
1.152
0.922
E2-06 (E4-06)
Motor Leakage Inductance
%
19
19.3
19.3
18.2
18.2
15.5
15.5
19.6
E2-10 (E4-10)
Motor Iron Loss for Torque Compensation
W
105
130
130
193
193
263
263
385
E5-01
Motor Code Selection
Hex.
FFFF
FFFF
1238
1238
123A
123A
123B
123B
L2-02
Momentary Power Loss Ride-Thru Time
s
0.5
0.5
0.5
0.5
0.8
0.8
1
1
L2-03
Momentary Power Loss Min. Baseblock Time
s
0.5
0.6
0.6
0.7
0.7
0.8
0.8
0.9
L2-04
Momentary Power Loss Voltage Recovery Time
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L8-02
Overheat Alarm Level
°
C
110
110
110
110
110
110
115
115
L8-35
Installation Method Selection
–
2
2
2
2
2
2
2
2
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
2
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
10
10
10
n5-02
Motor Acceleration Time
s
0.145
0.154
0.154
0.168
0.168
0.175
0.175
0.265
n9-12
On-Delay Compensation Time
μ
s
1.5
1.5
1.5
1.5
1.5
1.5
1.7
1.7
S6-01
DC Bus Capacity
μ
F
675
675
675
675
480
480
590
590
S6-02
Motor Acceleration Time
s
0.145
0.154
0.154
0.168
0.168
0.175
0.175
0.265
Содержание T1000A
Страница 4: ...4 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 32: ...1 5 Component Names 32 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 104: ...4 10 Test Run Checklist 104 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 334: ...7 5 Drive Replacement 334 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 362: ...A 6 Drive Derating Data 362 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...