B.3 Parameter Table
390
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
1B
Program lockout
Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned to the digital operator).
Closed: Parameters can be edited and saved.
20 to 2F
External fault
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
30
PID integral reset
Closed: Resets the PID control integral value.
31
PID integral hold
Open: Performs integral operation.
Closed: Maintains the current PID control integral value.
34
PID soft starter cancel
Open: PID soft starter is enabled.
Closed: Disables the PID soft starter b5-17.
35
PID input level selection
Closed: Inverts the PID input signal
40
Forward run command (2-wire sequence)
Open: Stop
Closed: Forward run
Note:
Cannot be set together with settings 42 or 43.
41
Reverse run command (2-wire sequence)
Open: Stop
Closed: Reverse run
Note:
Cannot be set together with settings 42 or 43.
42
Run command (2-wire sequence 2)
Open: Stop
Closed: Run
Note:
Cannot be set together with settings 40 or 41.
43
FWD/REV command (2-wire sequence 2)
Open: Forward
Closed: Reverse
Note:
Determines motor direction, but does not issue a Run command. Cannot be set together with settings 40 or
41.
44
Offset frequency 1
Closed: Adds d7-01 to the frequency reference.
45
Offset frequency 2
Closed: Adds d7-02 to the frequency reference.
46
Offset frequency 3
Closed: Adds d7-03 to the frequency reference.
50
Disturb Function Cancel
Open: Disturb function output is active.
Closed: Cancels the Disturb function.
51
Synchronous Accel/Decel
Closed: Assigns the same accel/decel times to all motors in the line so that they reach the desired frequency at the
same time.
53
Energy Saving On/Off
Closed: Enables the Energy Saving function.
H1 Multi-Function Digital Input Selections
H1-
Setting
Function
Description
Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
Содержание T1000A
Страница 4: ...4 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 32: ...1 5 Component Names 32 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 104: ...4 10 Test Run Checklist 104 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 334: ...7 5 Drive Replacement 334 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 362: ...A 6 Drive Derating Data 362 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...