5.6 F: Option Settings
174
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
n
F1-04, F1-10, F1-11: Operation at Speed Deviation (dEv), Detection Level, Delay Time
A speed deviation error (dEv) is triggered when the difference between the frequency reference and the speed feedback
exceeds the value set in F1-10 for longer than the time set in F1-1. The stopping method when a speed deviation fault
occurs can be selected in parameter F1-04.
Settings for Parameter F1-04:
Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only (drive continues operating while “dEv” flashes on the screen)
n
F1-05, F1-32: PG 1, PG 2 Rotation Selection
Determines the direction indicated by the pulses from the PG feedback encoder for motor 1 and motor 2.
See PG option card instruction manual for details on how to set the direction for the PG encoder and the motor.
Setting 0: A pulse leads with Forward run command.
Setting 1: B pulse leads with Forward run command.
n
F1-06, F1-35: PG 1, PG 2 Division Rate for PG Pulse Monitor
Sets the ratio between the pulse input and the pulse output of a PG option card as a three digit number, where the first
digit (n) sets the numerator and the second and third digit (m) set the denominator as shown below:
.
Example: To have a ratio of 1/32 between the PG card pulse input and output, set F1-06 = 032.
n
F1-12, F1-13, F1-33, F1-34: PG 1, PG 2 Gear Teeth 1, 2 (V/f w/PG only)
Sets the gear ratio between the motor shaft and the PG encoder. F1-12 and F1-33 set the number of gear teeth on the
motor side, while F1-13 and F-34 set the number of gear teeth for the load side. The drive uses the formula below to
calculate the motor speed.
Note:
A gear ratio of 1 will be used if any of these parameters is set to 0.
No.
Parameter Name
Option Port
Setting Range
Default
F1-04
Operation Selection at Deviation (dEv)
CN5-B, CN5-C
0 to 3
3
F1-10
Excessive Speed Deviation Detection Level
CN5-B, CN5-C
0 to 50%
10%
F1-11
Excessive Speed Deviation Detection Delay Time
CN5-B, CN5-C
0.0 to 10.0 s
0.5 s
No.
Parameter Name
Option Port
Setting Range
Default
F1-05
PG 1 Rotation Selection
CN5-C
0, 1
Determined by A1-02
F1-32
PG 2 Rotation Selection
CN5-B
0, 1
0
No.
Parameter Name
Option Port
Setting Range
Default
F1-06
PG 1 Division Rate for PG Pulse Monitor
CN5-C
1 to 132 (1 to
)
1
F1-35
PG 2 Division Rate for PG Pulse Monitor
CN5-B
1 to 132 (1 to
)
1
No.
Parameter Name
Option Port
Setting Range
Default
F1-12
PG 1 Gear Teeth 1
CN5-C
0 to 1000
0
F1-13
PG 1 Gear Teeth 2
CN5-C
0 to 1000
0
F1-33
PG 2 Gear Teeth 1
CN5-B
0 to 1000
0
F1-34
PG 2 Gear Teeth 2
CN5-B
0 to 1000
0
f
Pulse Input
= f
Pulse Output
(1 + n)
m
1
32
1
32
r/min =
Input pulses from PG
×
60
Pulses per Rev (F1-01/31)
Load-side PG gear teeth (F1-12/33)
Motor-side PG gear teeth (F1-13/34)
Содержание T1000A
Страница 4: ...4 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 32: ...1 5 Component Names 32 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 104: ...4 10 Test Run Checklist 104 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 334: ...7 5 Drive Replacement 334 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 362: ...A 6 Drive Derating Data 362 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...