5.10 o: Operator Related Settings
YASKAWA ELECTRIC
SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
249
P
a
ra
me
te
r D
e
ta
ils
5
n
o4-09: IGBT Maintenance Setting
Sets the value of the IGBT maintenance time displayed in U4-07 as a percentage of the total expected performance life.
This value should be reset to 0 when the IGBTs have been replaced.
Note:
The actual maintenance time will depend on the environment where the drive is used.
n
o4-11: U2, U3 Initialization
When the drive is initialized, the fault trace and fault history monitors (U2-
and U3-
) are not reset. Parameter
o4-11 can be used to reset them.
Setting 0: No action
The drive keeps the record already saved concerning fault trace and fault history.
Setting 1: Reset fault data
Resets the data for the U2-
and U3-
monitors. Once o4-11 is set to 1 and the ENTER key is pressed, fault data is
erased and the display returns to 0.
n
o4-12: kWh Monitor Initialization
The kWh monitors U4-10 and U4-11 are not initialized when power is shut off or the drive is initialized. Use o4-12 to
manually reset them.
Setting 0: No Action
The kWh data are kept as they are.
Setting 1: Reset kWh Data
Resets the kWh counter. The monitors U4-10 and U4-11 will display “0” after they are initialized. Once o4-12 is set to 1
and the ENTER key is pressed, kWh data is erased and the display returns to 0.
n
o4-13: Number of Run Commands Counter Initialization
The Run command counter displayed in U4-02 is not reset when the power is cycled or the drive is initialized. Use o4-13
to reset U4-02.
Setting 0: No Action
The Run command data are kept as they are.
Setting 1: Number of Run Commands Counter
Resets the Run command counter. The monitor U4-02 will show 0. Once o4-13 is set to 1 and the ENTER key is pressed,
the counter value is erased and the display returns to 0.
No.
Name
Setting Range
Default
o4-09
IGBT Maintenance Setting
0 to 150%
0%
No.
Name
Setting Range
Default
o4-11
U2, U3 Initialization
0 or 1
0
No.
Name
Setting Range
Default
o4-12
kWh Monitor Initialization
0 or 1
0
No.
Name
Setting Range
Default
o4-13
Number of Run Commands Counter Initialization
0 or 1
0
Содержание T1000A
Страница 4: ...4 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 32: ...1 5 Component Names 32 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 104: ...4 10 Test Run Checklist 104 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 334: ...7 5 Drive Replacement 334 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 362: ...A 6 Drive Derating Data 362 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...