5.8 L: Protection Functions
216
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
n
L1-03: Motor Overheat Alarm Operation Selection (PTC input)
Sets the drive operation when the PTC input signal reaches the motor overheat alarm level (oH3).
Setting 0: Ramp to stop
The drive stops the motor using the deceleration time 1 set in parameter C1-02
.
Setting 1: Coast to stop
The drive output is switched off and the motor coasts to stop.
Setting 2: Fast Stop
The drive stops the motor using the Fast Stop time set in parameter C1-09.
Setting 3: Alarm only
The operation is continued and an oH3 alarm is displayed on the digital operator.
n
L1-04: Motor Overheat Fault Operation Selection (PTC input)
Sets the drive operation when the PTC input signal reaches the motor overheat fault level (oH4).
Setting 0: Ramp to stop
The drive stops the motor using the deceleration time 1 set in parameter C1-02
.
Setting 1: Coast to Stop
The drive output is switched off and the motor coasts to stop.
Setting 2: Fast Stop
The drive stops the motor using the Fast Stop time set in parameter C1-09.
n
L1-05: Motor Temperature Input Filter Time (PTC input)
Used to set a filter on the PTC input signal in order to prevent a motor overheat fault from being mistakenly detected.
n
L1-13: Continuous Electrothermal Operation Selection
Determines whether or not to hold the current value of the electrothermal motor protection (L1-01) when the power
supply is interrupted.
Setting 0: Disabled
Setting 1: Enabled
No.
Name
Setting Range
Default
L1-03
Motor Overheat Alarm Operation Selection (PTC input)
0 to 3
3
No.
Name
Setting Range
Default
L1-04
Motor Overheat Fault Operation Selection (PTC input)
0 to 2
1
No.
Name
Setting Range
Default
L1-05
Motor Temperature Input Filter Time (PTC input)
0.00 to 10.00 s
0.20 s
No.
Name
Setting Range
Default
L1-13
Continuous Electrothermal Operation Selection
0 or 1
1
Содержание T1000A
Страница 4: ...4 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 32: ...1 5 Component Names 32 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 104: ...4 10 Test Run Checklist 104 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 334: ...7 5 Drive Replacement 334 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 362: ...A 6 Drive Derating Data 362 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...