6.5 Alarm Detection
290
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
Communications cable is disconnected or damaged.
• Check the connector to make sure the cable has a signal.
• Replace the communications cable.
Digital Operator Display
Minor Fault Name
CrST
Fault Reset with Run Command Enabled
Fault Reset Attempt with Run Command
Cause
Possible Solutions
Attempted to reset a fault with the Run command
still enabled.
• Ensure that a Run command cannot be entered from the external terminals or option card during fault reset.
• Turn off the Run command.
Digital Operator Display
Minor Fault Name
dEv
Speed Deviation (when using a PG option card)
The deviation between the speed reference and speed feedback is greater than the setting in F1-10 for longer than the time in F1-11.
Cause
Possible Solutions
Load is too heavy
Reduce the load.
Acceleration and deceleration times are set too short. Increase the acceleration and deceleration times (C1-01 through C1-08).
The load is locked up.
Check the machine.
Parameter settings are inappropriate.
Check the settings of parameters F1-10 and F1-11.
Incorrect speed feedback scaling if terminal RP is
used as speed feedback input in V/f Control.
• Set H6-02 to value of the speed feedback signal frequency when the motor runs at the maximum speed.
• Adjust the speed feedback signal using parameters H6-03 through H6-05.
• Make sure the speed feedback signal frequency does not exceed he maximum input frequency of terminal RP.
The motor brake engaged.
Ensure the brake releases properly.
Digital Operator Display
Minor Fault Name
dnE
Drive Disabled
Cause
Possible Solutions
“Drive Enable” is set to a multi-function contact
input (H1-
= 6A) and that signal was switched
off.
Check the operation sequence.
Digital Operator Display
Minor Fault Name
EF
Forward/Reverse Run Command Input Error
Both forward run and reverse run closed simultaneously for over 0.5 s.
Cause
Possible Solutions
Sequence error
Check the forward and reverse command sequence and correct the problem.
Note:
When minor fault EF detected, motor ramps to stop.
Digital Operator Display
Minor Fault Name
EF0
Option Card External Fault
An external fault condition is present.
Cause
Possible Solutions
An external fault was received from the PLC with
F6-03 = 3 (causing the drive to continue running
when an external fault occurs).
• Remove the cause of the external fault.
• Remove the external fault input from the PLC.
There is a problem with the PLC program.
Check the PLC program and correct problems.
Digital Operator Display
Minor Fault Name
EF1
External fault (input terminal S1)
External fault at multi-function input terminal S1.
EF2
External fault (input terminal S2)
External fault at multi-function input terminal S2.
EF3
External fault (input terminal S3)
External fault at multi-function input terminal S3.
EF4
External fault (input terminal S4)
External fault at multi-function input terminal S4.
EF5
External fault (input terminal S5)
External fault at multi-function input terminal S5.
EF6
External fault (input terminal S6)
External fault at multi-function input terminal S6.
EF7
External fault (input terminal S7)
External fault at multi-function input terminal S7.
EF8
External fault (input terminal S8)
External fault at multi-function input terminal S8.
Cause
Possible Solutions
An external device has tripped an alarm function.
Remove the cause of the external fault and reset the multi-function input value.
Wiring is incorrect.
• Ensure the signal lines have been connected properly to the terminals assigned for external fault detection (H1-
= 2C to 2F).
• Reconnect the signal line.
Multi-function contact inputs are set incorrectly.
• Check if the unused terminals have been set for H1-
= 2C to 2F (External Fault).
• Change the terminal settings.
Содержание T1000A
Страница 4: ...4 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 32: ...1 5 Component Names 32 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 104: ...4 10 Test Run Checklist 104 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 334: ...7 5 Drive Replacement 334 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 362: ...A 6 Drive Derating Data 362 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...