TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
239
No.
(Hex.)
Name
Description
Default
(Range)
Y4-42
(3D23)
Output Disconnect Detection
Sel
This parameter applies only when in Drive Mode. It sets the drive response if the connection between
the drive and the motor is disconnected.
0 : Disabled
1 : Alarm - Speed Search
2 : Alarm - Start at Zero
3 : Fault
Note:
1.
Loss Of Load
[Z1-31 to Z1-36]
, Load Verify
[Z1-53]
, and Bypass Energy Savings
[Z1-16]
can interfere with the correct operation of Output Disconnect Detection.
2.
When the Output Disconnect is active, the drive internally disables Output Phase Loss
Detection of more than one phase.
0
(0 - 3)
Y4-43
(3D24)
Output Disconnect Inject
Current
Sets the level of DC injection current during output disconnect as a percentage of the drive rated
current.
30%
(5 - 50%)
◆
YA: Preset Setpoint
No.
(Hex.)
Name
Description
Default
(Range)
YA-01
(3E58)
RUN
Setpoint 1
Sets the PID Setpoint when
b1-01 = 0 [Frequency Reference Selection 1 = Keypad or Multi-Speed
Selection]
.
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-
39 [PID User Unit Display Digits]
set the unit, range, and resolution.
0.00
(0.00 - 600.00)
YA-02
(3E59)
RUN
Setpoint 2
Sets the PID Setpoint as specified by the Multi-Setpoint digital inputs.
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-
39 [PID User Unit Display Digits]
set the unit, range, and resolution.
0.00
(0.00 - 600.00)
YA-03
(3E5A)
RUN
Setpoint 3
Sets the PID Setpoint as specified by the Multi-Setpoint digital inputs.
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-
39 [PID User Unit Display Digits]
set the unit, range, and resolution.
0.00
(0.00 - 600.00)
YA-04
(3E5B)
RUN
Setpoint 4
Sets the PID Setpoint as specified by the Multi-Setpoint digital inputs.
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-
39 [PID User Unit Display Digits]
set the unit, range, and resolution.
0.00
(0.00 - 600.00)
◆
YC: Foldback Features
No.
(Hex.)
Name
Description
Default
(Range)
YC-01
(3EBC)
Output Current Limit Select
Sets the function to enable or disable the output current regulator.
0 : Disabled
1 : Enabled
0
(0, 1)
YC-02
(3EBD)
RUN
Current Limit
Sets the current limit.
Note:
Value is internally limited to 300% of the drive rated current set in
n9-01 [Inverter Rated
Current]
.
0.0 A
(0.0 - 1000.0 A)
◆
YF: PI Auxiliary Control
No.
(Hex.)
Name
Description
Default
(Range)
YF-01
(3F50)
PI Aux Control Selection
Sets the PI Auxiliary Control function.
0 : Disabled
1 : Enabled
0
(0, 1)
YF-02
(3F51)
RUN
PI Aux Control Transducer
Scale
Sets the full scale (10 V or 20 mA) output of the pressure transducer connected to the analog input
terminal programmed for
H3-xx = 27 [PI Aux Control Feedback Level]
.
Note:
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level Decimal Place
Pos]
set the unit and resolution.
145.0
(1.0 - 6000.0)
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...