Setting Value
Function
Description
52
Sequence Timer Cancel
Sets the command to cancel the currently active Sequence Timer.
ON : Cancel Active Sequence Timer
61
Speed Search from Fmax
Sets the function to start speed search using an external reference although
b3-01 = 0 [Speed Search Selection at Start = Disabled]
.
Note:
The drive will detect
oPE03 [Multi-Function Input Setting Err]
when
H1-xx = 61 and 62
are set at the same time.
62
Speed Search from Fref
Sets the function to use an external reference to start speed search although
b3-01 = 0 [Speed Search Selection at Start = Disabled]
.
Note:
The drive will detect
oPE03 [Multi-Function Input Setting Err]
when
H1-xx = 61 and 62
are set at the same time.
63
Field Weakening
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in
d6-01 [Field
Weakening Level] and d6-02 [Field Weakening Frequency Limit]
when the input terminal is activated.
68
High Slip Braking (HSB)
Activate
Sets the command to use high-slip braking to stop the motor.
6A
Drive Enable
Sets the function to show
dnE [Drive Enabled]
on the keypad and ignore Run commands when the terminal is OFF.
70
Drive Enable 2
Sets the function to show
dnE [Drive Enabled]
on the keypad and ignore Run commands when the terminal is OFF.
ON : Run command is accepted.
OFF : Run command is disabled. When the drive is running, it stops according to
b1-03
setting.
82
PI Switch to Aux
Sets
YF-xx [PI Auxiliary Control]
parameters as primary PI loop parameters and disables
b5-xx [PID Control]
.
Note:
When this input is active,
YF-xx [PI Auxiliary Control]
parameters will always be the primary PI loop parameters. Parameter
YF-20 [PI Aux Main PI Speed Control]
does not have an effect.
83
Dedicated Multi-Setpoint
YA-02
Sets the function to set the PID setpoint to
YA-02 [Setpoint 2]
.
Note:
If you use this function and one of
H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2]
at the same time, the drive will detect an
oPE03 [Multi-Function Input Setting Err]
.
ON :
YA-02
is PID setpoint.
OFF :
YA-01 [Setpoint 1]
,
YA-03 [Setpoint 3]
, or
YA-04 [Setpoint 4]
is PID setpoint.
84
Dedicated Multi-Setpoint
YA-03
Sets the function to set the PID setpoint to
YA-03 [Setpoint 3]
. Set this function and
H1-xx = 83 [Dedicated Multi-Setpoint YA-02]
at
the same time.
Note:
If you use this function and one of
H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2]
at the same time, the drive will detect an
oPE03 [Multi-Function Input Setting Err]
.
ON :
YA-03
is PID setpoint.
OFF :
YA-01 [Setpoint 1]
,
YA-02 [Setpoint 2]
, or
YA-04 [Setpoint 4]
is PID setpoint.
85
Dedicated Multi-Setpoint
YA-04
Sets the function to set the PID setpoint to
YA-04 [Setpoint 4]
. Set this function,
H1-xx = 83 [Dedicated Multi-Setpoint YA-02]
, and
H1-xx = 84 [Dedicated Multi-Setpoint YA-03]
at the same time.
Note:
If you use this function and one of
H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2]
at the same time, the drive will detect an
oPE03 [Multi-Function Input Setting Err]
.
ON :
YA-04
is PID setpoint.
OFF :
YA-01 [Setpoint 1]
,
YA-02 [Setpoint 2]
, or
YA-03 [Setpoint 3]
is PID setpoint.
88
Thermostat Fault
Sets the drive to show the
VLTS [Thermostat Fault]
when the input terminal is ON.
Note:
This function is active when the drive is running.
A8
PI2 Control Disable
Sets the command to disable the PI2 Control function. Parameter
S3-12 [PI2 Control Disable Mode Sel]
sets the output
performance.
ON : Enabled
OFF : Disabled
AA
PI2 Control Inverse
Operation
Sets the command to change the sign of the PI2 Control input.
AB
PI2 Control Integral Reset
Sets the command to reset the PI2 Control integral value.
Note:
This input has priority over
H1-xx = AC [MFDI Function Selection = PI2 Control Integral Hold]
.
AC
PI2 Control Integral Hold
Sets the command to lock the PI2 Control integral value.
AD
Select PI2 Control PI
Parameters
Sets the command to use the
S3-06 [PI2 Control Proportional Gain]
and
S3-07 [PI2 Control Integral Time]
values instead of the
b5-02 [Proportional Gain (P)]
and
b5-03 [Integral Time (I)]
values. Set
S3-01 = 0 [PI2 Control Enable Selection = Disabled]
to
enable this function.
Note:
This multi-function input does not have an effect on PI2 Control. Use this input for the primary PI controller (
b5-xx
).
B9
Disable Pre-charge
Sets the command to disable the Pre-charge function.
ON : Pre-charge function is disabled
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...