YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
237
No.
(Hex.)
Name
Description
Default
(Range)
Y2-03
(3C66)
RUN
Sleep Delay Time
Sets the delay time before the drive enters Sleep Mode when the drive is at the sleep level set in
Y2-
02 [Sleep Level]
.
5 s
(0 - 3600 s)
Y2-04
(3C67)
RUN
Sleep Activation Level
Sets the level above which the output frequency must increase to activate the Sleep Function when
Y2-01 = 0, 3, or 5 [Sleep Level Type = Output Frequency, Output Speed (RPM), or Output
Frequency (non-PID)]
.
Note:
When you set this parameter to 0.0, this function will not be active, and the Sleep Function will
activate above the minimum speed (largest value from
d2-02 [Frequency Reference Lower
Limit]
,
Y1-06 [Minimum Speed]
, and
Y4-12 [Thrust Frequency]
).
0.0
(0.0 - 6000.0)
Y2-05
(3C68)
RUN
Sleep Boost Level
Sets the quantity of boost that the drive applies to the setpoint before it goes to sleep.
Note:
Set this parameter to 0.00 to disable Sleep Boost Function.
0.00%
(0.00 - 600.00%)
Y2-06
(3C69)
RUN
Sleep Boost Hold Time
Sets the length of time that the drive will keep the boosted pressure before it goes to sleep.
5.0 s
(0.5 - 160.0 s)
Y2-07
(3C6A)
RUN
Sleep Boost Max Time
Sets the length of time that the system (feedback) has to reach the boosted setpoint. The system must
reach the boosted setpoint in the time set in this parameter, or it will go to sleep.
20.0 s
(1.0 - 160.0 s)
Y2-08
(3C6B)
RUN
Delta Feedback Drop Level
Sets the level of the PID Error (set-point minus feedback) to deactivate the Sleep Mode operation.
Note:
Set this parameter to 0.00 to disable the function.
0.00%
(0.00 - 600.00%)
Y2-09
(3C6C)
RUN
Feedback Drop Detection
Time
Sets the time during which the software monitors the feedback to detect a flow/no-flow condition.
Refer to
Y2-08 [Delta Feedback Drop Level]
for more information.
10.0 s
(0.0 - 3600.0 s)
Y2-23
(3C7A)
RUN
Anti-No-Flow Bandwidth
Sets the quantity of PI error bandwidth that the drive uses to detect an Anti- No-Flow condition.
Note:
Do not set this parameter value too high, because operation can become unstable.
0.00%
(0.00 - 2.00%)
Y2-24
(3C7B)
RUN
Anti-No-Flow Detection
Time
Sets the time delay before the drive starts the increased deceleration rate after it detects Anti-No-
Flow.
10.0 s
(1.0 - 60.0 s)
Y2-25
(3C7C)
RUN
Anti-No-Flow Release Level Sets the amount below the setpoint which the feedback must decrease before the drive will disengage
Anti-No-Flow and return to normal PI operation.
Note:
The display unit and scaling change when the System Units change.
0.30%
(0.00 - 10.00%)
◆
Y4: Application Advanced
No.
(Hex.)
Name
Description
Default
(Range)
Y4-01
(3CFA)
RUN
Pre-Charge Level
Sets the level at which the drive will activate the pre-charge function when the drive is running at the
frequency set in
Y4-02 [Pre-Charge Frequency]
.
Note:
The drive will stop when one of these conditions is true:
•
The feedback level increases to more than
Y4-01
•
The pre-charge time set in
Y4-03 [Pre-Charge Time]
expires
0.00%
(0.00 - 600.00%)
Y4-02
(3CFB)
RUN
Pre-Charge Frequency
Sets the frequency at which the pre-charge function will operate.
0.0 Hz
(0.0 - 400.0 Hz)
Y4-03
(3CFC)
RUN
Pre-Charge Time
Sets the length of time that the Pre-Charge function will run.
Note:
Set this parameter to 0.0 to disable the function.
0.0 min
(0.0 - 3600.0 min)
Y4-05
(3CFE)
RUN
Pre-Charge Loss of Prime
Level
Sets the level at which the drive will detect loss of prime in the pump.
0.0 A
(0.0 - 1000.0 A)
Y4-11
(3D04)
RUN
Thrust Acceleration Time
Sets the time at which the drive output frequency will ramp up to the reference frequency set in
Y4-
12 [Thrust Frequency]
.
1.0 s
(0.0 - 600.0 s)
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...