2.3 Narrow Bypass Installation Position and Clearances
YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
25
2.3
Narrow Bypass Installation Position and Clearances
◆
Installation Dimensions
Refer to the Dimension Drawing (DD.HB.x.xx.xx) packaged with the bypass for exterior and mounting dimensions
for your model.
◆
Installation Position
Install the bypass vertically for sufficient cooling airflow.
A - Vertical installation
B - Horizontal installation
Figure 2.1 Installation Position
◆
Single Narrow Bypass Installation Clearances
Use the clearances specified in
to install the bypass. Make sure that there is sufficient space for wiring and
airflow.
A - 50 mm (2 in) minimum
B - 30 mm (1.2 in) minimum
C - 120 mm (4.7 in) minimum
D - Airflow direction
Figure 2.2 Single Bypass Installation
*1
This is the distance from a component or mounting bracket that has the maximum height. The highest component is different for different
models.
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...