YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
177
7.3
b: Application
◆
b1: Operation Mode Selection
No.
(Hex.)
Name
Description
Default
(Range)
b1-01
(0180)
Frequency Reference
Selection 1
Sets the input method for the frequency reference.
0 : Keypad
1 : Analog Input
2 : Serial Communications
3 : Option PCB
1
(0 - 3)
b1-02
(0181)
Run Command Selection 1
Sets the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : Serial Communications
3 : Option PCB
7 : AUTO C Term Run
8 : AUTO C Serial Run
9 : AUTO C Option Run
7
(0 - 9)
b1-03
(0182)
Stopping Method Selection
Sets the method to stop the motor after removing a Run command or entering a Stop command.
0 : Ramp to Stop
1 : Coast to Stop
2 : DC Injection Braking to Stop
3 : Coast to Stop with Timer
1
(0 - 3)
b1-04
(0183)
Reverse Operation Selection
Sets the reverse operation function. Disable reverse operation in fan or pump applications where
reverse rotation is dangerous.
0 : Reverse Enabled
1 : Reverse Disabled
1
(0, 1)
b1-08
(0187)
Run Command Select in
PRG Mode
Sets the conditions for the drive to accept a Run command entered from an external source when
using the keypad to set parameters.
0 : Disregard RUN while Programming
1 : Accept RUN while Programming
2 : Allow Programming Only at Stop
0
(0 - 2)
b1-11
(01DF)
Run Delay @ Stop
Sets the amount of time that the drive will not accept the Run command again after the Run
command is lost.
Note:
•
This parameter will operate for both AUTO Mode and HAND Mode.
•
This parameter will operate when the drive goes to sleep then wakes up.
•
The time set in this parameter does not apply for faults or Auto-Restarts.
•
When there is an active Run command while the time set in
b1-11
is active, the keypad will
show a
[Start Delay]
message as specified by the
o1-82 [Message Screen Display]
display
format.
0.0 s
(0.0 - 6000.0 s)
b1-12
(01E0)
Run Delay Memory
Selection
Sets how the drive saves the Run Delay Timer to the EEPROM during power loss.
0 : Disabled
1 : Only at Stop
2 : Running & Stop
2
(0 - 2)
b1-17
(01C6)
Run Command at Power Up
Sets drive response when you apply power to drive that has an external Run command. Set this
parameter in applications where energizing or de-energizing the drive enables the Run command.
0 : Disregard Existing RUN Command
1 : Accept Existing RUN Command
1
(0, 1)
b1-40
(3BCF)
Deceleration Abort Time
Sets the maximum time until the drive shuts off the output to decelerate to stop.
Note:
Set this parameter to 0.0 s to disable this function.
0.0 s
(0.0 - 6000.0 s)
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...