YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
195
No.
(Hex.)
Name
Description
Default
(Range)
H1-76
(39F0)
RUN
Terminal S6 Off-Delay Time Sets the length of time necessary for Terminal S6 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-77
(39F1)
RUN
Terminal S7 Off-Delay Time Sets the length of time necessary for Terminal S7 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
◆
H1-xx: MFDI Setting Values
Setting Value
Function
Description
3
Multi-Step Speed Reference
1
Uses speed references
d1-01 to d1-08
to set a multi-step speed reference.
4
Multi-Step Speed Reference
2
Uses speed references
d1-01 to d1-08
to set a multi-step speed reference.
5
Multi-Step Speed Reference
3
Uses speed references
d1-01 to d1-08
to set a multi-step speed reference.
6
Jog Reference Selection
Sets the drive to use the JOG Frequency Reference (JOG command) set in
d1-17 [Jog Reference]
. The JOG Frequency Reference
(JOG command) overrides the
d1-01 to d1-08 [References 1 to 8]
settings.
7
Accel/Decel Time Selection
1
Sets the drive to use
Acceleration/Deceleration Time 1 [C1-01, C1-02]
or
Acceleration/Deceleration Time 2 [C1-03, C1-04]
.
8
Baseblock Command (N.O.)
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
ON : Baseblock (drive output stop)
OFF : Normal operation
9
Baseblock Command (N.C.)
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
ON : Normal operation
OFF : Baseblock (drive output stop)
A
Accel/Decel Ramp Hold
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output frequency that was
stored in the drive at the time of the pause, and restarts motor operation.
B
Overheat Alarm (oH2)
Sets the drive to display an
oH2 [Drive Overheat Warning]
alarm when the input terminal is ON. The alarm does not have an effect
on drive operation.
C
Analog Terminal Enable
Selection
Sets the command that enables or disables the terminals selected in
H3-14 [Analog Input Terminal Enable Sel]
.
ON : Input to the terminal selected with
H3-14
is enabled
OFF : Input to the terminal selected with
H3-14
is disabled
F
Not Used
Use this setting for unused terminals or to use terminals in through mode.
14
Fault Reset
Sets the command to reset the current fault when the Run command is inactive.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before trying to reset a
fault.
15
Fast Stop (N.O.)
Sets the command to ramp to stop in the deceleration time set in
C1-09 [Fast Stop Time]
when the input terminal is activated while
the drive is operating.
17
Fast Stop (N.C.)
Sets the command to ramp to stop in the deceleration time set in
C1-09 [Fast Stop Time]
when the input terminal is activated while
the drive is operating.
18
Timer Function
Sets the command to start the timer function. Use this setting with
Timer Output [H2-xx = 12]
.
19
PID Disable
Sets the command to disable PID control when
b5-01 = 1 or 3 [PID Mode Setting = Standard or Fref + PID Trim]
.
ON : PID control disabled
OFF : PID control enabled
1B
Programming Lockout
Sets the command to prevent parameter changes when the terminal is OFF.
ON : Programming Lockout
OFF : Parameter Write Prohibit
1E
Reference Sample Hold
Sets the command to sample the frequency reference at terminals A1 or A2 and hold the frequency reference at that frequency.
20
External Fault (NO-Always-
Ramp)
When the terminal activates, the drive ramps to stop in the selected deceleration time. Fault relay output terminal MA-MC will turn
ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is stopped or running.
21
External Fault (NC-Always-
Ramp)
When the terminal deactivates, the drive ramps to stop in the selected deceleration time. Fault relay output terminal MA-MC will
turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is stopped or running.
22
External Fault (NO-@Run-
Ramp)
When the terminal activates during run, the drive ramps to stop in the selected deceleration time. Fault relay output terminal MA-
MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while the drive is stopped.
23
External Fault (NC-@Run-
Ramp)
When the terminal deactivates during run, the drive ramps to stop in the selected deceleration time. Fault relay output terminal MA-
MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while the drive is stopped.
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...