3.5 Bypass PCB Control Circuit
48
YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
◆
Bypass Control Circuit Wire Gauges and Tightening Torques
Use the tables in this section to select the correct wires. Use shielded wire to wire the control circuit terminal block.
Use crimp ferrules on the wire ends to make the wiring procedure easier and more reliable.
Table 3.3 Bypass Control Circuit Wire Gauges and Tightening Torques
Bypass Terminal
Block
Terminal
Tightening Torque
in
∙
lb
Recommended Gauge
AWG
Applicable Gauge
AWG
TB1
DO-7 - DO-10
4
18
26-14
TB2
DI-1 - DI-8, IG24, SHIELD
TB3
SHEILD, TXRX-, TXRX+, IG5
TB4
+10 Vdc, AI-1, COMMON
TB6
GROUND, GROUND
◆
Crimp Ferrules
Attach an insulated sleeve when you use crimp ferrules. Refer to
for the recommended external dimensions
and model numbers of the crimp ferrules.
Use the CRIMPFOX 6, a crimping tool made by PHOENIX CONTACT.
Figure 3.7 External Dimensions of Crimp Ferrules
Table 3.4 Crimp Ferrule Models and Sizes
Wire Gauge
mm
2
(AWG)
Model
L (mm)
L1 (mm)
φ
d1 (mm)
φ
d2 (mm)
0.25 (24)
AI 0.25-8YE
12.5
8
0.8
2.0
0.34 (22)
AI 0.34-8TQ
12.5
8
0.8
2.0
0.5 (20)
AI 0.5-8WH
AI 0.5-8OG
14
8
1.1
2.5
0.75 (18)
AI 0.75-8 GY
14
8
1.3
2.8
◆
Bypass Control Circuit Terminal Block Input Functions
WARNING!
Sudden Movement Hazard. Correctly wire and test all control circuits to make sure that the control circuits operate
correctly. If you use a drive that has incorrect control circuit wiring or operation, it can cause death or serious injury.
WARNING!
Sudden Movement Hazard. Check the I/O signals and the external sequences for the drive before you set the
Application Preset function. When you set the Application Preset function (A1-06
≠
0), it changes the I/O terminal functions for the
drive and it can cause equipment to operate unusually. This can cause serious injury or death.
NOTICE:
Damage to Equipment. Do not energize and de-energize the bypass more frequently than one time each 30 minutes. If
you frequently energize and de-energize the bypass, it can cause failure.
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...