YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
205
Setting Value
Function
Description
19F
!High PI Auxiliary Control
Level
The terminal deactivates when the PI Aux Feedback Level is more than
YF-12 [PI Aux Control High Level Detect]
or if the drive
detects an
HIAUX [High PI Aux Feedback Level]
fault.
1A9
!RELAY Operator Control
The terminal changes to OFF or ON when you push the RELAY (
) button. When the terminal is ON, push
to turn
it OFF. When the terminal is OFF, push
to turn in ON.
1AB
!Thrust Mode
The terminal deactivates when the output frequency is between 0.0 Hz and the value set in
Y4-12 [Thrust Frequency]
and the Thrust
Bearing function is active.
1AC
!Setpoint Not Maintained
The terminal deactivates when the drive detects
NMS [Setpoint Not Met]
condition.
1B2
!BAS Interlock
The terminal deactivates when the Run command is active or the drive is outputting the voltage. The drive will use this as an
actuation signal for an external damper.
1B8
!Pump Fault
The terminal deactivates when one of these faults is active:
LFB [Low Feedback Sensed]
,
HFB [High Feedback Sensed]
,
NMS
[Setpoint Not Met]
, or
EFx [External Fault (Terminal Sx)]
.
1B9
!Transducer Loss
The terminal deactivates when the current into the analog input associated with PID feedback is more than 21 mA or less than 3
mA, or an
FDBKL [WIRE Break]
Fault or an
FDBKL [Feedback Loss Wire Break]
Alarm is active.
1BA
!PI Auxiliary Control Active The terminal deactivates when the PI Auxiliary Controller has an effect on the output speed.
1BB
!Differential Feedback
Exceeded
The terminal deactivates when the difference between the PID Feedback and the value from the terminal set for
H3-xx = 2D
[Differential Feedback]
is more than
Y4-18 [Differential Level]
for the time set in
Y4-19 [Differential Lvl Detection Time]
.
1BC
!Sleep Active
The terminal deactivates when the Sleep function is active and the drive is not operating.
Note:
The terminal will not deactivate for Sleep Boost function.
1BD
!Start Delay
The terminal deactivates when the Feedback is more than the start level or the Feedback is less than the Inverse PID and the start
timer is timing.
Note:
You must set
Y1-04 [Sleep Wake-up Level] ≠ 0
and
Y1-05 [Sleep Wake-up Level Delay Time] ≠ 0
to use this function.
1BE
!Pre-Charge
The terminal deactivates when the drive is in Pre-Charge Mode.
1C0
!HAND Mode
The terminal deactivates when the drive is in HAND Mode operation.
1C1
!AUTO Mode
The terminal deactivates when the drive is in AUTO Mode operation.
1C2
!OFF Mode
The terminal deactivates when the drive is in OFF Mode operation.
1C3
!Main Feedback Lost
The terminal deactivates when the drive loses the main PID feedback.
1C4
!Backup Feedback Lost
The terminal deactivates when the drive loses the backup PID feedback.
◆
H3: Analog Inputs
No.
(Hex.)
Name
Description
Default
(Range)
H3-01
(0410)
Terminal A1 Signal Level
Select
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
2 : 4 to 20 mA
3 : 0 to 20 mA
0
(0 - 3)
H3-02
(0434)
Terminal A1 Function
Selection
Sets the function for MFAI terminal A1.
0
(0 - 31)
H3-03
(0411)
RUN
Terminal A1 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A1.
100.0%
(-999.9 - +999.9%)
H3-04
(0412)
RUN
Terminal A1 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A1.
0.0%
(-999.9 - +999.9%)
H3-09
(0417)
Terminal A2 Signal Level
Select
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
2 : 4 to 20 mA
3 : 0 to 20 mA
2
(0 - 3)
H3-10
(0418)
Terminal A2 Function
Selection
Sets the function for MFAI terminal A2.
Note:
The default setting for
H3-10
changes when
b5-01 [PID Mode Setting]
changes:
•
b5-01 = 0 [Disabled]
: 0
•
b5-01 ≠ 0
: B
Determined by b5-01
(0 - 31)
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...