72
YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
4.1
Section Safety
DANGER
Electrical Shock Hazard
Do not examine, connect, or disconnect wiring on an energized bypass. Before servicing,
disconnect all power to the equipment and wait for the time specified on the warning label at a
minimum. The internal capacitor stays charged after the bypass is de-energized. The charge
indicator LED extinguishes when the DC bus voltage decreases below 50 Vdc. When all indicators
are OFF, remove the covers before measuring for dangerous voltages to make sure that the bypass
is safe.
If you do work on the bypass when it is energized, it will cause serious injury or death from electrical shock.
WARNING
Electrical Shock Hazard
Do not operate the bypass when covers are missing. Replace covers and shields before you
operate the bypass. Use the bypass only as specified by the instructions.
Some figures in this section include bypasses without covers or safety shields to more clearly show the inside of the
bypass. If covers or safety shields are missing from the bypass, it can cause serious injury or death.
Do not remove covers or touch circuit boards while the bypass is energized.
If you touch the internal components of an energized bypass, it can cause serious injury or death.
NOTICE
Sudden Movement Hazard
Deactivate the Run command before you switch from Programming Mode to Drive Mode.
If you switch from Programming Mode to Drive Mode and there is an active Run command, the motor will rotate
and the equipment can suddenly start.
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...