194
YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
7.8
H: Terminal Functions
◆
H1: Digital Inputs
No.
(Hex.)
Name
Description
Default
(Range)
H1-01
(0438)
Terminal S1 Function
Selection
Sets the function for MFDI terminal S1.
40
(3 to 1A8)
H1-02
(0439)
Terminal S2 Function
Selection
Sets the function for MFDI terminal S2.
F
(3 to 1A8)
H1-03
(0400)
Terminal S3 Function
Selection
Sets the function for MFDI terminal S3.
24
(3 to 1A8)
H1-04
(0401)
Terminal S4 Function
Selection
Sets the function for MFDI terminal S4.
14
(3 to 1A8)
H1-05
(0402)
Terminal S5 Function
Selection
Sets the function for MFDI terminal S5.
3
(3 to 1A8)
H1-06
(0403)
Terminal S6 Function
Selection
Sets the function for MFDI terminal S6.
4
(3 to 1A8)
H1-07
(0404)
Terminal S7 Function
Selection
Sets the function for MFDI terminal S7.
6
(3 to 1A8)
H1-61
(39E1)
RUN
Terminal S1 On-Delay Time
Sets the length of time necessary for Terminal S1 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
H1-62
(39E2)
RUN
Terminal S2 On-Delay Time
Sets the length of time necessary for Terminal S2 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
H1-63
(39E3)
RUN
Terminal S3 On-Delay Time
Sets the length of time necessary for Terminal S3 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
H1-64
(39E4)
RUN
Terminal S4 On-Delay Time
Sets the length of time necessary for Terminal S4 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
H1-65
(39E5)
RUN
Terminal S5 On-Delay Time
Sets the length of time necessary for Terminal S5 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
H1-66
(39E6)
RUN
Terminal S6 On-Delay Time
Sets the length of time necessary for Terminal S6 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
H1-67
(39E7)
RUN
Terminal S7 On-Delay Time
Sets the length of time necessary for Terminal S7 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
H1-71
(39EB)
RUN
Terminal S1 Off-Delay Time Sets the length of time necessary for Terminal S1 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-72
(39EC)
RUN
Terminal S2 Off-Delay Time Sets the length of time necessary for Terminal S2 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-73
(39ED)
RUN
Terminal S3 Off-Delay Time Sets the length of time necessary for Terminal S3 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-74
(39EE)
RUN
Terminal S4 Off-Delay Time Sets the length of time necessary for Terminal S4 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-75
(39EF)
RUN
Terminal S5 Off-Delay Time Sets the length of time necessary for Terminal S5 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...