4.3 Start-up, Test Operation, and Rotation Check
84
YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
4.
Push
to give the bypass a Run command from HAND Mode. Make sure that
Ub-01 [Motor Current]
is
not more than the nameplate FLA. It is normal for the current be more than full load amps temporarily at start.
Watch and listen for unusual conditions or noises.
5.
Look at the motor (or load) to make sure that the rotation direction is correct (Bypass Mode). If you cannot
determine the rotation direction, push
and watch the motor as it coasts to stop.
If the motor direction in Bypass Mode is
CORRECT
, the test is complete.
If the motor direction in Bypass Mode is
INCORRECT
, do steps 6 to 11.
6.
Push
to stop the motor.
7.
De-energize the system at the power source. Observe correct lockout/tagout safety procedures and wait for
the CHARGE light to completely go out on the HV600.
8.
Remove lower cover (or open cabinet door) to access motor wiring.
9.
Switch any two phases on the
customer connection side of incoming power
.
Note:
• DO NOT change the motor (output) wiring.
• DO NOT change the wiring connected directly to the HV600 drive unit.
10.
Replace lower cover (or close cabinet door).
11.
Repeat Steps 1 to 5 of this procedure to confirm correct rotation in Bypass Mode.
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...