7.11 o: Keypad-Related Settings
222
YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
◆
o2: Keypad Operation
No.
(Hex.)
Name
Description
Default
(Range)
o2-02
(0506)
OFF Key Function Selection
Sets the function to use
on the keypad to stop the drive when the Run command source for
the drive is REMOTE (external) and not assigned to the keypad.
0 : Disabled
1 : Enabled
1
(0, 1)
o2-03
(0507)
User Parameter Default
Value
Sets the function to keep the settings of changed parameters as user parameter defaults to use during
initialization.
0 : No change
1 : Set defaults
2 : Clear all
0
(0 - 2)
o2-04
(0508)
Drive Model (KVA)
Selection
Sets the Drive Model code. Set this parameter after you replace the control board.
Determined by the drive
(-)
o2-05
(0509)
Home Mode Freq Ref Entry
Mode
Sets the function that makes it necessary to push
to use the keypad to change the frequency
reference value while in Drive Mode.
0 : ENTER Key Required
1 : Immediate / MOP-style
0
(0, 1)
o2-06
(050A)
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive or
if you damage the cable while the keypad is the Run command source.
0 : Disabled
1 : Enabled
1
(0, 1)
o2-09
(050D)
Reserved
-
-
o2-19
(061F)
Parameter Write during Uv
Enables and disables the function to change parameter settings during a
Uv [DC Bus Undervoltage]
condition.
0 : Disabled
1 : Enabled
0
(0, 1)
o2-24
(11FE)
LED Light Function
Selection
Sets the function to show the LED status rings and keypad LED lamps.
Note:
When you use
A1-03 [Initialize Parameters]
to initialize the drive, the drive will not reset this
parameter.
0 : Enable Status Ring & Keypad LED
1 : LED Status Ring Disable
2 : Keypad LED Light Disable
0
(0 - 2)
o2-27
(1565)
bCE Detection Selection
Sets drive operation if the Bluetooth device is disconnected when you operate the drive in Bluetooth
Mode.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use
C1-09
)
3 : Alarm Only
4 : No Alarm Display
3
(0 - 4)
◆
o3: Copy Keypad Function
No.
(Hex.)
Name
Description
Default
(Range)
o3-01
(0515)
Copy Keypad Function
Selection
Sets the function that saves and copies drive parameters to a different drive with the keypad.
0 : Copy Select
1 : Backup (drive → keypad)
2 : Restore (keypad → drive)
3 : Verify (check for mismatch)
4 : Erase (backup data of keypad)
0
(0 - 4)
o3-02
(0516)
Copy Allowed Selection
Sets the copy function when
o3-01 = 1 [Copy Keypad Function Selection = Backup (drive →
keypad)]
.
0 : Disabled
1 : Enabled
0
(0, 1)
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...