226
YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
No.
(Hex.)
Name
Description
Default
(Range)
S2-05
(320A)
Timer 1 Reference Source
Selects the frequency reference source to run the drive when sequence timer 1 is active (only
applicable when
S2-04 > 0 [Timer 1 Sequence Selection ≠ Digital Out Only]
).
0 : Operator (d1-01/YA-01)
1 : Operator (d1-02/YA-02)
2 : Operator (d1-03/YA-03)
3 : Operator (d1-04/YA-04)
4 : Terminals
5 : Serial Com
6 : Option PCB
8 : Set by b1-01
Note:
For reference source 0 to 3, the drive will use
d1-xx
frequency reference when PID mode is
disabled and
YA-xx
setpoint when PID is enabled.
0
(0 - 8)
S2-06
(320B)
Timer 2 Start Time
Sets the start time for timer 2.
Note:
•
Default is when
o4-22 = 1 [Time Format = 12 Hour Clock]
. When
o4-22 = 0 [24 Hour Clock]
,
default is 00:00. When
o4-22 = 2 [12 Hour JP Clock]
, default is 00:00 AM.
•
Range is when
o4-22 = 1
. When
o4-22 = 0
, range is 00:00 to 24:00. When
o4-22 = 2
, range is
00:00 AM to 11:59 PM.
12:00
(12:00 AM - 11:59 PM)
S2-07
(320C)
Timer 2 Stop Time
Sets the stop time for timer 2.
Note:
•
Default is when
o4-22 = 1 [Time Format = 12 Hour Clock]
. When
o4-22 = 0 [24 Hour Clock]
,
default is 00:00. When
o4-22 = 2 [12 Hour JP Clock]
, default is 00:00 AM.
•
Range is when
o4-22 = 1
. When
o4-22 = 0
, range is 00:00 to 24:00. When
o4-22 = 2
, range is
00:00 AM to 11:59 PM.
12:00
(12:00 AM - 11:59 PM)
S2-08
(320D)
Timer 2 Day Selection
Sets the days for which sequence timer 2 is active.
0 : Timer disabled
1 : Daily
2 : Mon - Fri
3 : Sat - Sun
4 : Monday
5 : Tuesday
6 : Wednesday
7 : Thursday
8 : Friday
9 : Saturday
10 : Sunday
0
(0 - 10)
S2-09
(320E)
Timer 2 Sequence Selection
Sets the drive response when sequence timer 2 is active.
0 : Digital Out Only
1 : Run
2 : Run - PID Disable
0
(0 - 2)
S2-10
(320F)
Timer 2 Reference Source
Selects the frequency reference source to run the drive when sequence timer 2 is active (only
applicable when
S2-09 > 0 [Timer 2 Sequence Selection ≠ 0]
).
0 : Operator (d1-01/YA-01)
1 : Operator (d1-02/YA-02)
2 : Operator (d1-03/YA-03)
3 : Operator (d1-04/YA-04)
4 : Terminals
5 : Serial Com
6 : Option PCB
8 : Set by b1-01
Note:
For reference source 0 to 3, the drive will use
d1-xx
frequency reference when PID mode is
disabled and
YA-xx
setpoint when PID is enabled.
0
(0 - 8)
S2-11
(3210)
Timer 3 Start Time
Sets the start time for timer 3.
Note:
•
Default is when
o4-22 = 1 [Time Format = 12 Hour Clock]
. When
o4-22 = 0 [24 Hour Clock]
,
default is 00:00. When
o4-22 = 2 [12 Hour JP Clock]
, default is 00:00 AM.
•
Range is when
o4-22 = 1
. When
o4-22 = 0
, range is 00:00 to 24:00. When
o4-22 = 2
, range is
00:00 AM to 11:59 PM.
12:00
(12:00 AM - 11:59 PM)
S2-12
(3211)
Timer 3 Stop Time
Sets the stop time for timer 3.
Note:
•
Default is when
o4-22 = 1 [Time Format = 12 Hour Clock]
. When
o4-22 = 0 [24 Hour Clock]
,
default is 00:00. When
o4-22 = 2 [12 Hour JP Clock]
, default is 00:00 AM.
•
Range is when
o4-22 = 1
. When
o4-22 = 0
, range is 00:00 to 24:00. When
o4-22 = 2
, range is
00:00 AM to 11:59 PM.
12:00
(12:00 AM - 11:59 PM)
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...