YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
139
Code
Name
Causes
Possible Solutions
OD
Output Disconnect
The output circuit between the drive and the motor is
open, and the drive output current is less than 5% of
E2-01 [Motor Rated Current (FLA)]
.
•
Close the disconnected output circuit between the drive and the
motor.
•
If you do not use a motor disconnect, set
Y4-42 = 0 [Disabled]
.
Note:
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
•
If the drive detects this error, it will respond as specified by the setting of
Y4-42 [Output Disconnect Detection Sel]
.
Code
Name
Causes
Possible Solutions
oH
Heatsink Overheat
The ambient temperature is high and the heatsink
temperature is more than the
L8-02 [Overheat Alarm
Level]
.
•
Measure the ambient temperature.
•
Increase the airflow around the drive.
•
Install a cooling device (cooling fan or air conditioner) to
decrease the ambient temperature.
•
Remove objects near the drive that are producing too much heat.
There is not sufficient airflow around the drive.
•
Give the drive the correct installation space as shown in the
manual.
•
Make sure that there is sufficient circulation around the control
panel.
•
Examine the drive for dust or other unwanted materials that
could clog the cooling fan.
•
Remove unwanted materials that prevent air circulation.
The internal cooling fan or fans stopped.
1.
Replace the cooling fan.
2.
Set
o4-03 = 0 [Fan Operation Time Setting = 0 h]
to reset the
cooling fan operation time.
Note:
•
The drive detects this error if the heatsink temperature of the drive is more than
L8-02
.
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
•
Use
L8-03 [Overheat Pre-Alarm Selection]
to the stopping method for this fault.
Code
Name
Causes
Possible Solutions
oH2
External Overheat (H1-XX=B)
An external device sent an
oH2
alarm.
1.
Find the external device that output the overheat alarm.
2.
Remove the cause of the problem.
3.
Clear the
Overheat Alarm (oH2) [H1-xx = B]
in MFDI
terminals S1 to S7.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
oH3
Motor Overheat (PTC Input)
The thermistor wiring that detects motor temperature
is defective.
Correct wiring errors.
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault
The motor has overheated.
•
Check the load level, acceleration/deceleration time, and motor
start/stop frequency (cycle time).
•
Decrease the load.
•
Increase the values set in
C1-01 to C1-04 [Acceleration/
Deceleration Times]
.
•
Set
E2-01 [Motor Rated Current (FLA)]
correctly to the value
specified by the motor nameplate.
•
Make sure that the motor cooling system is operating correctly,
and repair or replace it if it is damaged.
•
Adjust
E1-04 to E1-10 [V/f Pattern Parameters]
. Decrease the
values set in
E1-08 [Mid Point A Voltage]
and
E1-10 [Minimum
Output Voltage]
.
Note:
If the values set in
E1-08
and
E1-10
are too low, the overload
tolerance will decrease at low speeds.
Note:
•
When
H3-02 or H3-10 = E [MFAI Function Selection = Motor Temperature (PTC Input)]
, the drive detects this fault if the motor overheat signal entered to analog input terminals
A1 and A2 is more than the alarm detection level.
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
•
If the drive detects this error, it will operate the motor as specified by the stopping method set in
L1-03 [Motor Thermistor oH Alarm Select]
.
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...