Mounting conditions
Mounting place
-
In the control cabinet
Mounting position
-
Horizontal and vertical
EMC
Standard
Comment
Emitted interfer-
ence
EN 61000-6-4
Class A (Industrial area)
Noise immunity
zone B
EN 61000-6-2
Industrial area
EN 61000-4-2
ESD
8kV at air discharge (degree of severity 3),
4kV at contact discharge (degree of severity
2)
EN 61000-4-3
HF field immunity (casing)
80MHz … 1000MHz, 10V/m, 80% AM (1kHz)
1.4GHz ... 2.0GHz, 3V/m, 80% AM (1kHz)
2GHz ... 2.7GHz, 1V/m, 80% AM (1kHz)
EN 61000-4-6
HF conducted
150kHz … 80MHz, 10V, 80% AM (1kHz)
EN 61000-4-4
Burst, degree of severity 3
EN 61000-4-5
Surge, installation class 3 *
*) Due to the high-energetic single pulses with Surge an appropriate external protective circuit with lightning protection elements like conductors
for lightning and overvoltage is necessary.
VIPA System SLIO FM 050
Basics and Assembly
General data
HB300 | FM | 050-1BA00 | GB | 15-11
31