The electronic power section supply is internally protected
against higher voltage by fuse. The fuse is within the
power module. If the fuse releases, its electronic module
must be exchanged!
n
The power section supply is to be externally protected with a fuse,
which corresponds to the maximum current. This means max. 10A
is to be protected with a 10A fuse (fast) respectively by a line cir-
cuit breaker 10A characteristics Z!
n
It is recommended to externally protect the electronic power
supply for bus coupler and I/O area with a 2A fuse (fast) respec-
tively by a line circuit breaker 2A characteristics Z.
n
The electronic power supply for the I/O area of the power module
007-1AB10 should also be externally protected with a 1A fuse
(fast) respectively by a line circuit breaker 1A characteristics Z.
After PowerON of the System SLIO the LEDs RUN respectively MF
get on so far as the sum current does not exceed 3A.
With a sum current greater than 3A the LEDs may not be activated.
Here the power module with the order number 007-1AB10 is to be
placed between the peripheral modules.
If the 10A for the power section supply is no longer sufficient, you
may use the power module from VIPA with the order number
007-1AB00. So you have also the possibility to define isolated
groups.
The power module with the order number 007-1AB10 is to be used if
the 3A for the electronic power supply at the backplane bus is no
longer sufficient. Additionally you get an isolated group for the DC
24V power section supply with 4A.
By placing the power module 007-1AB10 at the following backplane
bus modules may be placed with a sum current of max. 2A. After-
wards the power module 007-1AB10 is to be placed again. To secure
the power supply, the power modules may be mixed used.
Fusing
State of the electronic
power supply via LEDs
Deployment of the
power modules
Power module
007-1AB00
VIPA System SLIO FM 050
Basics and Assembly
Wiring
HB300 | FM | 050-1BA00 | GB | 15-11