SW gate:
Open (activate):
in user program by edge 0-1 SW_GATE_SET in the
control word
Close (deactivate):
in user program by edge 0-1 SW_GATE_RESET in the
control word
The following behavior for the output channel may be set via the
parameterization:
n
No comparison: output is not influenced
n
Counter value
³
comparison value
: output is set
n
Counter value
£
comparison value
: output is set
n
Counter value
=
comparison value
: output is set
Please consider that the output may only be controlled, when the bit
STS_CTRL_DO in the
counter status
is set.
4.2 In-/Output area
4.2.1 Input area 12byte
At CPU, PROFIBUS and PROFINET the input respectively output
area is embedded to the corresponding address area.
IX - Index for access via CANopen
SX - Subindex (6000h + EtherCAT-Slot) for access via EtherCAT
More can be found in the according manual of your bus coupler.
Addr. Name
Bytes
Function
IX
SX
+0
CV_I
4
Counter value
5400h
01h
+4
CL_I
4
Latch value
5401h
02h
+8
CSTS_I
2
Counter status
5402h
03h
+10
C_US
2
µs ticker
5403h
04h
The
counter value
always contains the current value of the counter.
With an edge 0-1 at the Latch input the recent
counter value
is stored
at
Latch value
.
Bit
Name
Function
0
STS_SYNC
Reset was active
1
STS_CTRL_DO Is set
when digital output is enabled
2
STS_SW-GATE Status software gate
(set when
SW gate
is active)
Counter output
Input area
12byte
CV_I Counter value
CL_I Latch value
CSTS_I Counter status
VIPA System SLIO FM 050
Deployment
In-/Output area > Input area 12byte
HB300 | FM | 050-1BA00 | GB | 15-11
42