Gate control via SW/HW gate, interrupting
SW gate
HW gate
Reaction Counter
edge 0-1
1
Continue
1
edge 0-1
Continue
Gate control via
SW/HW gate
, operating mode "Count once": If the
internal gate has been closed automatically it may only be opened
again under the following conditions:
SW gate
HW gate
Reaction I gate
1
edge 0-1
1
edge 0-1
(after edge 0-1
at HW gate)
1
1
As soon as during a count process an edge 0-1 is recognized at the
"Latch" input of the counter, the recent
counter value
is stored in the
latch register. You may access the latch register via the
input area
.
After a STOP-RUN transition latch is always 0.
The
compare value
is to be pre-defined by CC_I. As soon as a com-
parison condition is kept, the bit STS_DO of the counter status is set.
Please consider that the bit STS_DO may only be influenced when in
the
counter status
the bit STS_CTRL_DO is set. You pre-define the
behavior of the counter output via the parameterization (MODE2_I):
n
output never switches
n
output switches when
counter value
³
comparison value
n
output switches when
counter value
£
comparison value
n
output switches at
comparison value
Output never switches
The output never switches.
Output switches when counter value
³
comparison value
The output remains set as long as the
counter value
is higher or
equal
comparison value
.
Output switches when counter value
£
comparison value
The output remains set as long as the counter value is lower or equal
comparison value.
Pulse at comparison value
When the counter reaches the
comparison value
the output is set for
the parameterized
pulse duration
. If the pulse duration = 0 the output
is set until the comparison condition is no longer met. When you've
set a main counting direction the output is only set at reaching the
comparison value
from the main counting direction.
Pulse duration
Gate control "Count
once"
Latch function
Comparison
VIPA System SLIO FM 050
Deployment
Counter additional functions
HB300 | FM | 050-1BA00 | GB | 15-11
56