Bit
Name
Function
3
STS_RST
Status reset input
4
STS_STRT
Status hardware gate
(set when
HW gate
is active)
5
STS_GATE
Status internal gate
(set when internal gate active)
6
STS_DO
Status digital counter output (DO)
7
STS_C_DN
Status set
at counter direction backward
8
STS_C_UP
Status set
at counter direction forward
9
STS_CMP*
Status comparison is set
when the comparison condition is met.
If comparison is parameterized
never
,
the bit is never set
10
STS_END*
Status is set
when
end value
was reached
11
STS_OFLW*
Status is set at overflow
12
STS_UFLW*
Status is set at underflow
13
STS_ZP*
Status is set at zero run
14
STS_LTCH
Status of the latch input
15
-
reserved
*) The bits remain set until reset with RES_SET (bit 6
control word
).
In the SLIO module there is a timer (µs ticker). With PowerON the
timer starts counting with 0. After 65535µs the timer starts with 0
again. With each change of the
counter value
the timer value is
stored as 16bit µs value together with the
counter value
in the
input
area
.
4.2.2 Output area 10byte
At CPU, PROFIBUS and PROFINET the output area is embedded to
the corresponding address area.
IX - Index for access via CANopen
SX - Subindex (7000h + EtherCAT-Slot) for access via EtherCAT
More can be found in the according manual of your bus coupler.
C_US µs ticker
Output area
VIPA System SLIO FM 050
Deployment
In-/Output area > Output area 10byte
HB300 | FM | 050-1BA00 | GB | 15-11