CAUTION!
Bus interface and power module of a head module may
not be separated!
Here you may only exchange the electronic module!
1.
Remove if exists the wiring of the head module.
.
2.
Press the unlocking lever at the lower side of the just mounted
right module and pull it forward.
3.
Turn all the locking lever of the head module to be exchanged
upwards.
4.
Pull the head module forward.
5.
For mounting turn all the locking lever of the head module to be
mounted upwards.
6.
To mount the head module put it to the left module and push it,
guided by the stripes, to the mounting rail.
7.
Turn all the locking lever downward again.
8.
Plug again the electronic module, which you have removed
before.
VIPA System SLIO FM 050
Basics and Assembly
Demounting and module exchange
HB300 | FM | 050-1BA00 | GB | 15-11