Name
Bytes
Function
Default
DS
IX
SX
NUMCH
1
Number channels
of the module
01h
08h
CHERR
1
Channel error
00h
09h
CH0ERR
1
Channel-specific error
00h
0Ah
CH1ERR…
CH7ERR
7
reserved
00h
0Bh ...
11h
DIAG_US
4
µs ticker
00h
13h
Byte
Bit 7 ... 0
0
n
Bit 0: set at module failure
n
Bit 1: reserved
n
Bit 2: set at external error
n
Bit 3: set at channel error
n
Bit 4: set at overload at output
n
Bit 7 ... 5: reserved
Byte
Bit 7 ... 0
0
n
Bit 3 ... 0: Module class
– 1000b: Function module
n
Bit 4: set at channel information present
n
Bit 7 ... 5: reserved
Byte
Bit 7 ... 0
0
reserved
Byte
Bit 7 ... 0
0
n
Bit 2 ... 0: reserved
n
Bit 3: set at internal diagnostics buffer overflow
n
Bit 5 ... 4: reserved
n
Bit 6: Process interrupt lost
n
Bit 7: reserved
Byte
Bit 7 ... 0
0
n
Bit 6 ... 0: Channel type
– 76h: Counter module
n
Bit 7: reserved
ERR_A Diagnostic
MODTYP Modul infor-
mation
ERR_C reserved
ERR_D Diagnostic
CHTYP Channel type
VIPA System SLIO FM 050
Deployment
Diagnostic and interrupt
HB300 | FM | 050-1BA00 | GB | 15-11
62