Order no.
050-1BA00
Current consumption from load voltage L+
(without load)
-
Output delay of "0" to "1"
30 µs
Output delay of "1" to "0"
30 µs
Minimum load current
-
Lamp load
10 W
Parallel switching of outputs for redundant con-
trol of a load
not possible
Parallel switching of outputs for increased
power
not possible
Actuation of digital input
ü
Switching frequency with resistive load
max. 10 kHz
Switching frequency with inductive load
max. 0.5 Hz
Switching frequency on lamp load
max. 10 kHz
Internal limitation of inductive shut-off voltage
L+ (-52 V)
Short-circuit protection of output
yes, electronic
Trigger level
1 A
Number of operating cycle of relay outputs
-
Switching capacity of contacts
-
Output data size
10 Byte
Technical data counters
Number of counters
1
Counter width
32 Bit
Maximum input frequency
100 kHz
Maximum count frequency
400 kHz
Mode incremental encoder
ü
Mode pulse / direction
ü
Mode pulse
-
Mode frequency counter
-
Mode period measurement
-
Gate input available
ü
Latch input available
ü
Reset input available
ü
Counter output available
ü
Status information, alarms, diagnostics
Status display
yes
Interrupts
yes, parameterizable
VIPA System SLIO FM 050
Hardware description
Technical data
HB300 | FM | 050-1BA00 | GB | 15-11
36