Alphabetical reference
Commands and Queries Reference
RAMP?
return the current Ramp Duration for the Power Module. The result is
a string in the following format: m:ss:nnn where m=minutes,
ss=seconds and nnn=mili-seconds.
Syntax
RAMP?
<ch>
Parameters
the number of the channel to be queried.
Category Settings
Type:
Sequential
RCL
restores settings of all the Power Modules.
Syntax
RCL
<int>
Parameters
a decimal number in the range 0 to 9 specifying the
storage number the XMP 2600 will restore the
settings from.
Category System
Type:
Overlapped
RCL?
return an indication whether the Storage Area is free (result is “0”) or
not (result is “1”).
Syntax
RCL?
<int>
Parameters
a decimal number in the range 0 to 9 specifying the
storage number to be checked.
Category System
Type:
Sequential.
RESET
reset the entire XMP 2600 system: resets the Power Modules and the
Main Controller.
Syntax
RESET
Parameters none
Category System
Type:
Sequential
RIPL
program the Power Module to simulate ripple at its output.
Syntax
RIPL
<ch>,<int>,<int>
Parameters
the number of the Power Module to be programmed.
level of ripple: a decimal number in the range 0 to 2,
selecting (respectively) one of the following levels:
off, low, high.
frequency of ripple: a decimal number in the range 1
to 7, selecting (respectively) one of the following
frequencies:
1 = 50Hz
2 = 60Hz
3 = 100Hz
4 = 120Hz
5 = 400Hz
6 = 800Hz
7 = 2khz
Category Settings
Type:
Sequential
58
XMP 2600 Programming Manual
rev. 1.1