Protective Elements
The directional decision depends on the layout of the mains star-point or the angle between residual voltage and
ground current. The residual voltage can be measured via suitable transformers (da-dn winding – formerly: e-n) or
can be calculated, provided the VTs are in star-connection.
The earth current can be measured either directly via a cable-type transformer or detected by a Holmgreen
connection. The earth current can alternatively be calculated from the phase currents; but this is only possible if the
phase currents are not ascertained by a V-connection.
The device can optionally be procured with a sensitive earth current measuring input (in preparation).
455
MRI4
DOK-HB-MRI4-2E