Protective Elements
Direct Commands of the Automatic Reclosure Module
Parameter
Description
Setting range
Default
Menu path
Res TotNo suc
unsuc
Reset all statistic AR counters: Total number
of AR, successful and unsuccessful no of AR.
inactive,
active
inactive
[Operation
/Reset]
Res Service Cr
Reset the Service Counters
inactive,
active
inactive
[Operation
/Reset]
Reset Lock via
HMI
Reset the AR Lockout via the panel.
inactive,
active
inactive
[Operation
/Reset]
Res Max Shots /
h Cr
Resetting the Counter for the maximum
allowed shots per hour.
inactive,
active
inactive
[Operation
/Reset]
Device Planning Parameters of the Module Automatic Reclosure
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
do not use
[Device planning]
527
MRI4
DOK-HB-MRI4-2E