Protective Elements
6
Lockout
An activated autoreclose function goes into the »L
OCKOUT
« state when one of the following conditions is true:
An unsuccessful autoreclose is detected after all programmed autoreclose shots. The fault is of permanent
nature.
Reclose failure (incomplete sequence)
Autoreclose rate per hour exceeds the limit
Fault timer elapses (tripping time too long)
Breaker failure during AR starting
Manual breaker close operation during autoreclose process
At least one protective function is still tripping before reclose command is issued
The autoreclose function exits the »L
OCKOUT
« state if the programmed lockout reset signal asserts and programmed
Lockout Reset timer elapses.
A Service Alarm (Service Alarm 1 or Service Alarm 2) will not lead to a lockout of the
AR function.