Protective Elements
Direct Commands of the Thermal Overload Module
Parameter
Description
Setting range
Default
Menu path
Reset
Reset the Thermal Replica
inactive,
active
inactive
[Operation
/Reset]
Device Planning Parameters of the Thermal Overload Module
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
do not use
[Device planning]
489
MRI4
DOK-HB-MRI4-2E
Содержание highprotec MRI4
Страница 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Страница 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Страница 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Страница 56: ...Installation and Connection Ethernet RJ45 Terminals 56 MRI4 DOK HB MRI4 2E 1 8 TxD TxD RxD n c n c RxD n c n c...
Страница 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Страница 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Страница 373: ...373 MRI4 DOK HB MRI4 2E...