Switchgear/Breaker – Manager
Parameter
Description
Setting range
Default
Menu path
t-TripCmd
Minimum hold time of the OFF-command
(circuit breaker, load break switch)
0 - 300.00s
0.2s
[Control
/SG
/SG[1]
/Trip Manager]
Latched
Defines whether the Binary Output Relay
will be Latched when it picks up.
inactive,
active
inactive
[Control
/SG
/SG[1]
/Trip Manager]
Ack TripCmd
Ack TripCmd
1..n,
Assignment List
-.-
[Control
/SG
/SG[1]
/Trip Manager]
Off Cmd1
Off Command to the Circuit Breaker if the
state of the assigned signal becomes true.
1..n, Trip Cmds I[1].TripCmd
[Control
/SG
/SG[1]
/Trip Manager]
Off Cmd2
Off Command to the Circuit Breaker if the
state of the assigned signal becomes true.
1..n, Trip Cmds -.-
[Control
/SG
/SG[1]
/Trip Manager]
Off Cmd3
Off Command to the Circuit Breaker if the
state of the assigned signal becomes true.
1..n, Trip Cmds -.-
[Control
/SG
/SG[1]
/Trip Manager]
Off Cmd4
Off Command to the Circuit Breaker if the
state of the assigned signal becomes true.
1..n, Trip Cmds -.-
[Control
/SG
/SG[1]
/Trip Manager]
Off Cmd5
Off Command to the Circuit Breaker if the
state of the assigned signal becomes true.
1..n, Trip Cmds -.-
[Control
/SG
/SG[1]
/Trip Manager]
Off Cmd6
Off Command to the Circuit Breaker if the
state of the assigned signal becomes true.
1..n, Trip Cmds -.-
[Control
/SG
/SG[1]
/Trip Manager]
406
MRI4
DOK-HB-MRI4-2E
Содержание highprotec MRI4
Страница 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Страница 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Страница 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Страница 56: ...Installation and Connection Ethernet RJ45 Terminals 56 MRI4 DOK HB MRI4 2E 1 8 TxD TxD RxD n c n c RxD n c n c...
Страница 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Страница 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Страница 373: ...373 MRI4 DOK HB MRI4 2E...